10
Display
Function Default
L2
Loop 2
Activatingthisparameter,anyloopthatis
connectedtotheLoop2inputwillserveasa
SAFETY/CLOSEfunction.
Y Loop 2 enabled
no Loop 2 disabled
(see note regarding Loop 1)
no
S1
Loop 1 sensitivity
Adjuststhesensitivityofthevehicledetection
loop
00 Minimumsensitivity
10 Maximumsensitivity
05
S2
Loop 2 sensitivity
Adjuststhesensitivityofthevehicledetection
loop
00 Minimumsensitivity
10 Maximumsensitivity
05
Mt
Motor movement
Usingthefunctionprovidedbythispara-
metermakesitpossibletomanuallymove
thebarrierbar,operatingasdead-man.
Pressing+willopentheautomatedsystem,
pressing-causestheautomatedsystemto
close.
oP pressing+,open
cL pressing -,close
--
St
AUTOMATED SYSTEM STATUS:
Thisallowsyoutochoosewhethertoquittheprogramme
and save the data.
Y=quitandsavethedata
no=quitwithoutsavingthedata
Onquittingtheprogramme,presstheFkeytodisplay
thestatusoftheautomatedsystem
00 Beam closed
01 Beam open
02 Stationaryreadytoopen
03 Stationaryreadytoclose
04 Automatedsystempaused
05 Opening
06 Closing
07 Failsafeinprogress
08 2-EASYdeviceverificationinprogress
09 Pre-flashingthenOPENS
10 Pre-flashingthenCLOSES
11 EMERGENCY Open
You can go to St at any time by simultaneously
pressing F and -.
Displaying of the automated system status
St is extremely
important for the installing/maintenance technician in order
to distinguish the logical processes that the board carries
out during movement.
If, for example, the automated system status is CLOSED,
the display MUST read
00. When the OPEN command is
received, the display will change to
09, if pre-ashing is
enabled, or directly to
05 (the OPENING movement) to then
display
01 once the position of gate OPEN is reached).
Exampleofastatussequencedisplayedstartingfromaclosedbarrier
00 Beam closed
05 Opening
01 Beam open /
04 Pause
06 Closing
The sequence does not include statuses 09 and 10 which
correspond to pre-flashing when opening and closing,
respectively.
5.2 Changing the predened parameters set
TheE680boardfeaturessixsetsofpre-definedconfigurationsthat
allowrapidadaptingtothesizeofthebeaminstalled,makingitthe
startingpointforafineadjustmentoftheparameters.Toselectone
oftheavailable configurations, you must change the parameter
dF from thepre-setvalue00(neutralcondition)tothevalue
correspondingto the barrier configuration(beamlength, type and
numberof accessories installed)shown inTables4or 5onpage
24(e.g. choosedefault 04for abeam measuring5 min length
withfootandlights).
Tocompleteconfiguration,itis necessary toexit the Basic
Configurationmenubypressing“F”untilparameterSt is reached
orbypressing“F”and“-”