11
FSW-CL
FSW-OPEN
Fig.3
This operation changes the value of the parameters So
and
SC in Basic conguration and FO, FC, oc
in Advanced conguration, setting them on the default
values as shown in the tables in paragraph 6.3.
Unlike the other parameters, the value of step
dF is
not stored, thus allowing access to the menu through a
neutral condition, which is the one displayed every time the
configuration menu is opened..
Ifyoudonotwishtoloadanysetofpre-definedparameters,leave
parameter St on 00andpress“F”togoontothenextparameter
Setting a set of pre-dened parameters that does not
correspond to the actual conguration of the barrier could
cause irreversible damage to the automated system, in
particular if the default corresponds to a beam length
shorter than the actual one.
5.3 BUS accessories menu
The E680 board is designed to connect up to 8 pairs of BUS
photocells.ForthebusdevicesconnectedtotheE680boardtobe
detectedandmanagedbyit,theymustbestoredontheboard.To
dothis,proceedasfollows:
• cutoffpowerfromtheboard.
• installandprogramtheaccessoriesusingthedesiredaddress,
dependingonthefunction you wish to use (as described in
paragraph4.1.2)
• poweruptheboard.
• accessBasicConfiguration,asdescribedinparagraph5.1
• onceprogrammingstepbuisreached,no,willbedisplayed,
indicatingthatherearenostoredbusdevices.
• toperformentry, simultaneously pressandhold the + and -
buttonsforatleast5seconds(duringthistime,thewritingno
will flash)
•
oncetheprocedureiscompleted,Y will appear as confirmation.
•
when+and-arereleased,thedisplaywillshowthecurrentstatus
oftheBUSdevices,ornoagain,ifthere arenoconnected
BUS devices.
Thefollowingimage(Fig.3)showsthecorrespondenceofthevarious
displaysegmentstothedifferenttypesofBUSdevicesthatcanbe
connectedtothesystem:
FSW CL: BUSphotocells placed to protect the gate
closingarea
OPEN: BUSphotocellsusedasOPENpulsegenerators
FromthedisplayofthestatusoftheBUSdevices,pressingthe+key
enablesthetypesofBUSdevicespresenttobeverified.
Forexample,thefollowingphotographshowssafetydevicespresent
duringclosingandapairofphotocellsfunctioningasopenpulse:
Fortheautomatedsystemtooperatecorrectly,thestatus
ofthesegmentsoftheleft-handdigitmustcorrespond
totheautomatedsystem at rest and without pulse
generatorsororsafetiesengaged.
WhentheCLOSEphotocellsareengaged,thebottom
segmentswillgoon,asshownintheimagetotheside.
IfthepairofOPEN pulse generator photocells is
engaged, the display will show the configuration of
segmentsshownintheimageonthesideofthepage,
inwhichthecorrespondingverticalsegmentison,and
willremainlikethisuntilthephotocellsaredisengaged.
Ifinvolved,thepairofOPENpulsegeneratorphotocells
commandsopening of the automated system and
preventsitfrom closing until it is disengaged, like a
normal OPEN pulse received through terminal board
J1(terminal3).
TheBUScommunicationsystemusesaself-diagnosticfunctionable
toprovideconnectionerrorsignalsorBUSaccessoriesconfiguration
errorsignal.
Thedisplaywillshowaflashingcc if there is a
shortcircuitalongtheBUSline,asshowninthe
figure.Tosolvetheproblemitisnecessaryto
carefullyverifyalltheconnectionsmade.
ThedisplaywillshowaflashingEr as shown
inthe imageon theside ofthe page,should
more than one pair of photocells have the
sameadressandincaseofacallingorfailsafe
error.Ensurethatthesettingsarecorrect,with
referencetotheindicationsgiveninparagraph
4.1.2
ThestatusoftheBUSandrelatedinputsignalscanalsobeseenby
analysingthetwoLEDsDL1(red)andDL2(green),whichmakeit
possibletoimmediatelyverifyifBUScommunicationisactiveorif
thereisanerror,andifthereareanyactiveinputsornot.Thestatus
oftheLEDscanbeverifiedinthefollowingtables:
J6
DL1 DL2
2Easy BUS
21
Busstatus(alwayson)