12
ENGLISH
DL1 LED description (Red)
On Atleastoneoftheinputs(safeties,OPENpulse)is
engagedoractive
Off No OPENinput is activeandno safety deviceis
engaged
DL2 LED description (Green)
On
fixed
Normallyactive(LEDoneveniftherearenodevices
connected)
Off
BUS-2EASYline short-circuited (flash every 2.5
sec.)
Rapid
flashing
An error has been detected in the BUS-2EASY
connection;repeattheacquisitionprocedure.Ifthe
errorpersists,checkthat:
• thesystemdoes not have more than one
accessorywiththesameaddress(see also
instructionsregardingtheaccessories)
• makesurethereisnocallingerror(numberof
devicesconnectedisgreaterorlessthanthat
storedduringsetup)
6. Advanced Conguration
ToaccessAdvanced Configuration, press F and, while holding it,
also press +:
• when
+isreleased,thenumberofthefirstavailablefunction
will appear
• when F
is also released, the value is displayed, and can be
changedusing+ and -
• pressingFagain,andholdingit,thenameofthenextparameter
will be displayed; when released, the value can be changed
using+ and -
• oncethelastfunctionhasbeenreached,pressingF makes it
possibletoeithersavethepreviouslychangedparametersorexit
withoutsavingthechanges;thedisplaywillgobacktoshowing
thestatusoftheinputs.
ADVANCED CONFIGURATION
Display Function
Default
FO
Opening motor power
Adjuststhethrustofthemotorduringtheope-
ningphase.
00 Minimumpower
50 Maximumpower
40
FC
Closing motor power
Adjuststhethrustofthemotorduringtheclosing
phase.
00 Minimumpower
50 Maximumpower
40
PF
Pre-flashing
Thisparameterisusedtoactivatetheflashing
lamp for 5 seconds before the selected
movement.
no disabled
OC before each movement
CL beforeeachclosingmovement
OP beforeeachopeningmovement
PA onlyattheendofthepause
no
Display
Function
Default
tP
Pre-flashing time
Pre-flashingtimeexpressedinseconds.
00 minimumpre-flashing
10 maximumpre-flashing
00
oc
Sensitivity of obstacle during closing
Thisdeterminesthe sensitivity to an obstacle
beforereversingtakesplace.
01 Minimumsensitivity
50 Maximumsensitivity
01
o1
Output 1
Settingthisfunctionmakesitpossibletomodify
the signal type of output 1, allowing high
connectionflexibilitywithexternaldevices.
00 Failsafe
01 TYPE 1 BEAM ILLUMINATION (output
active when beam closed, disabled
with bar open or paused, intermittent
whenmoving). Use only with output
4!
02 DISABLED
03 Beam CLOSED
04 BeamOPENorinPAUSE,itgoesoff
duringclosingpre-ashing.
05 BeaminOPENINGMOVEMENT,
includingpre-ashing.
06 BeaminCLOSINGMOVEMENT,
includingpre-ashing.
07 Beam STATIONARY
08 Beam in EMERGENCY mode
09 LOOP1engaged
10 LOOP2engaged
11 OPEN for E680 slave
12 CLOSE for E680 slave
13 Beam RELEASED
14 Notused
15 Notused
16 FCAengaged
17 FCCengaged
18 Notused
19 WARNING LAMP (on during opening
and pause, ashing when closing, off
whentheautomatedsystemisclosed)
04