12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-9
GENERAL SPECIFICATIONS
Operating specifications for the 12530/12540 are as follows:
Environmental
Operating temperature
32 - 120°F (0 - 49°C)
Relative humidity
Up to 85% @ 86°F (30°C)
Primary Supply
Primary Input Voltage:
120 VAC (50/60 Hz) nominal (12530/12540-120)
240 VAC (50/60 Hz) nominal (12530/12540-240)
Maximum primary input current:
3.0A at 120 VAC
1.5A at 240 VAC
Secondary and Trouble Power Supply
24 volt lead-acid battery set:
Maximum Charge Voltage: 28.0 VDC
Maximum Charge Current: 2.75 A
Maximum Input Current: 4.66A
Battery capacity: 7-38 A.H. (over 10 A.H. requires separate enclosure)
Auxiliary Power Outputs
Current:
0.9 amp maximum for remote annunciators
0.9 amp maximum for auxiliary power outputs, DACT power and option boards
Non-Resettable Power Outputs
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Resettable Power Output
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Addressable Device Circuits
Power limited
Supervised
Voltage: 24 VDC nominal
Maximum Current (shorted): 0.25A
Maximum wire loop resistance: 20 ohms/line
Faraday Addressable Devices:
Two Style 4 or 6 circuits
Expandable to four Style 4 or 6 circuits with optional boards
60 detectors and modules max.
System Sensor Devices:
Two Style 4, 6 or 7 circuits
Expandable to four Style 4, 6 or 7 circuits with optional boards
99 sensors (smoke, heat) max
99 monitor and control modules max.

Table of Contents