12530/12540 OWNER'S MANUAL
P/N 447203 Issue I III-5
12530/12540 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the System Alarm LED flashes, LCD will display alarm conditions and the panel buzzer
sounds. Local audible and visual signals and remote alarm signals operate.
When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel
are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic
signal has been received at the Fire Department.
Authorized Personnel Only
To silence the alarm:
To silence the notification appliances after evacuation, where permitted, operate the Button
Enable keyswitch and press the Alarm Silence switch. The notification appliances and panel
buzzer will be silenced, and LED indications will change from flashing to continuous. The Alarm
Silenced LED will be lit.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a
predetermined time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by operating
the Button Enable keyswitch pressing the System Reset switch.
Trouble Operation
Trouble is indicated by:
System Trouble LED flashes
LCD will display trouble conditions
Panel buzzer sounds
To silence the trouble buzzer:
Operate the Button Enable keyswitch and press the Trouble Silence switch. The Trouble
Silenced LED lights and the specific trouble LED(s) may change to continuous display. When the
trouble condition has been cleared, you may need to reset the panel to restore to a normal
standby condition.
Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not to
initiate a fire alarm sequence
Normal Standby Condition
The green AC Power On LED will be lit and no other indicators on.
For service, contact: ___________________________________________
Telephone Number: ___________________________________________
Frame these instructions and mount them near the control unit for operator reference.