12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-11
RS232 Printer Output
Power limited
Not supervised
Voltage Range: -15 VDC to +15 VDC
Maximum Current (shorted): 0.050A
Baud Rate: 4800
Maximum wire loop resistance: 25 ohms
Initiating Device Circuits (Optional board P/N 12503)
Expandable in groups of 4 to 8 Class B, Style B circuits with optional expansion boards
Convertible to Class A, Style D circuits with optional adapter
Power limited
Supervised
Standby Voltage Range: 16-27 VDC
Maximum Standby Current: 10.3 mA
Maximum Smoke Detector Current: 3 mA
Maximum Alarm Current: 48 mA
Maximum Ripple: 1.5 VAC
Maximum Wire Loop Resistance: 100 ohms
DACT Expansion Module (Optional module P/N 12513)
Power limited
Supervised for short or open circuit
Maximum Voltage: 60 VDC
Maximum Current (shorted): 0.100 A
Alarm Relay Board (Optional board P/N 12402)
Power limited
Contact Rating:
1 A, 30VDC maximum, resistive
0.5 A, 30VAC maximum, resistive