FS10 Series
Fluid Components International LLC 43
Bank Item # Item Name Description R/W Type Size
Default
Password
Level
1 HW_REV Hardware Version R int 1 N/A
2 FW_REV Firmware Revision R int 1 N/A
3 YY Date Code, Year R int 1 N/A
4 MM Date Code, Month R int 1 N/A
5 DD Date Code, Date R int 1 N/A
6 S_N Sequence Number R int 2 N/A
7 RESERVED1 Reserved 1 int 1
11 FREQ_MAX_OUT For output modes 2, 3, 6, & 7 sets the
maximum frequency output
R/W float 4 2000.0 Lev 2
12 UI_ENABLE User Interface enable:
0 = “normal” buttons and LEDs active
1 = “LEDs only”
2 = “power indicator LED only”
3 = “all LEDs on” (test mode)
4 = “non” neither buttons nor LEDs
active
R/W int 1 0 Lev 2
14 BTN_ENTER_TIMEOUT Keypad lockout time period (sec) R/W int 2 3 Lev 2
35 TAG Customer Tag Number R/W char. 20 Lev 2
36 UNITS_K Conversion factor applied to
flow_final_out to compute
flow_final_units
R/W float 4 1.0 Lev 2
37 UNITS_ID Units identifier associated with
UNITS_K conversion factor
R/W char. 10 SFPS Lev 2
38 PIPE_ID
User Field: Pipe identification
R/W char. 20 Lev 2
39 USER_ID2 User identification field R/W char. 20 Lev 2
40 USER_ID3 User identification field R/W char. 20 Lev 2
41 USER_ID4 User identification field R/W char. 20 Lev 2
45 RTD_TYPE Reference sensor RTD type: 1= 1000
ohm, 2= 500 ohm, 3= 100ohm
R/W int 1 1 Lev 2
46 NAMUR_ENABLE Enables/Disables NAMUR_Level
(0=disabled; 1= enabled low, <3.6 mA ;
2= enabled high, >21 mA)
R/W int 1 0 Lev 2
49 TEMP_UNITS Temperature units for param. #238:
0 = Degrees F, 1 = Degrees C.
R/W int 1 0 Lev 2
50 QSM1_BANK Quick setup mode bank for button 1 R/W int 1 .05 Lev 2
52 QSM1_PERCENT_SPAN Default switch point level as percent of
established span
R/W float 4 30 Lev 2
53 QSM2_BANK Quick setup mode bank for button 2 R/W int 1 .05 Lev 2
Table 8 – RS232 Interface Reference Table