EasyManua.ls Logo

Festo CMSH - Page 73

Festo CMSH
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Festo — CMSH — 2021-10
Malfunctions
73
ID Message NAM
UR
1)
Possible cause Notes/remedies
1174 Covered distance
limit armature
exceeded
2)
Set threshold value
exceeded
Process valve service life
reached
Oscillating behaviour
Repeated position drift
and readjustment due to
severe compressed air
leakage
Service the process valve
and replace if necessary.
Optimise control parame-
ters.
1184 Number of move-
ments armature
exceeded
2)
Set threshold value
exceeded
Process valve service life
reached
Oscillating behaviour
Repeated position drift
and readjustment due to
severe compressed air
leakage
Service the process valve
and replace if necessary.
Optimise control parame-
ters.
1187 Number of direction
changes armature
exceeded
2)
Set threshold value
exceeded
Process valve service life
reached
Stick-Slip behaviour
Repeated position drift
and readjustment due to
severe compressed air
leakage
Service the process valve
and replace if necessary.
Check drive and/or
process valve for changes
in friction.
1298 Initialization failed:
Incorrect potentiom-
eter value
Drive outside the oper-
ating range of the potenti-
ometer
Check whether the posi-
tioner is correctly mounted
on the drive.
With external potentiom-
eter: check attachment
position of the potentiom-
eter.

Other manuals for Festo CMSH

Related product manuals