EasyManua.ls Logo

Festo CMSH - Page 76

Festo CMSH
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76
Festo — CMSH — 2021-10
Malfunctions
ID Message NAM
UR
1)
Possible cause Notes/remedies
1330 Initialization failed:
Position sensing
Increased sensor noise
Drive outside the oper-
ating range of the potenti-
ometer
Defective potentiometer
External potentiometer
outside specification
Compressed air leakage at
the drive or positioner
Incorrect or missing pneu-
matic connection of the
drive
Incorrect configuration of
the safety position
Repeat initialisation. In
case of repeated failure,
contact Festo Support
è
www.festo.com/sp.
Check whether the posi-
tioner is correctly mounted
on the drive.
With external potentiom-
eter: check attachment
position of the potentiom-
eter.
Check specification of the
external potentiometer.
Check pneumatic connec-
tion.
Check configuration of the
safety position.
1350 Pressure sensor
failure
Defective electronics
Contact Festo Support
è
www.festo.com/sp.
1556 Initialization running
Ongoing initialisation
Wait for completion of ini-
tialisation.
If necessary, cancel initiali-
sation manually.
1557 Digital input active:
Substitute target
position
2)
Active signal at the digital
input
1558 Digital input active:
End position
requested
2)
Active signal at the digital
input
1596 Manual operation
Operation of the posi-
tioner in manual mode
1597 Manual operation
Operation of the posi-
tioner in manual mode
1) Corresponds to NAMUR recommendation NE 107
2) Can be changed by the user
Tab. 87: Messages

Other manuals for Festo CMSH