D. Modbus
®
TCP objects of the CPX-FB36
D-12
Festo CPX-FB36-EN en 1611a English
Modbus®
address
1)
Pneumatic interface for CPA pneumatic set to 1 ... 22 valves
Inputs process data Outputs process data
Bit 15 12 11 8 7 4 3 0 15 12 11 8 7 4 3 0
n Echo outputs 0 … 15 Outputs 0 … 15
n+1 x Echo outputs
16 … 22
x Outputs 16 … 22
n+2 Diagnostic data –
1) n corresponds to the first Modbus® address of the module.
Tab. D/17: Pneumatic interface for CPA pneumatic (1 ... 22 valves)
Modbus®
address
1)
Pneumatic interface for Midi/Maxi pneumatic set to 1 ... 8 valves
Inputs process data Outputs process data
Bit 15 12 11 8 7 4 3 0 15 12 11 8 7 4 3 0
n x Echo outputs x Outputs
n+1 Diagnostic data –
1) n corresponds to the first Modbus® address of the module.
Tab. D/18: Pneumatic interface for Midi/Maxi pneumatic (1 ... 8 valves)