57
System default parameters
Temperature Detector
Default values
Label
See note (**)
Enablement
Enabled
LED blink
On
Assigned zone
(see: "Zone
assignment)
Base type
Normal
Use zone setting
Yes
Day operating mode
A2S
Night operating mode
A2S
Smoke Detector
Default values
Label
See note (**)
Enablement
Enabled
LED blink
On
Assigned zone
(see: "Zone
assignment)
Base type
Normal
Use zone setting
Yes
Day smoke sensitivity
Medium
Night smoke sensitivity
Medium
Smoke + Temperature
Detector
Default values
Label
See note (**)
Enablement
Enabled
LED blink
On
Assigned zone
(see: "Zone
assignment)
Base type
Normal
Use zone setting
Yes
Day temp. operating
mode
A2S
Day smoke operating
mode
Normal
Day smoke sensitivity
Medium
Night temp. operating
mode
A2S
Night smoke operating
mode
Normal
Night smoke sensitivity
Medium
CO + Temperature
Detector
Default values
Label
See note (**)
Enablement
Enabled
Led blink
On
Assigned zone
(see: "Zone
assignment)
Base type
Normal
Use zone setting
Yes
Day temp. operating
mode
A2S
Day CO operating
Normal
mode
Day CO
sensitivity
Medium
Night temp.
operating mode
A2S
Night CO mode
Normal
Night CO
sensitivity
Medium
Modules
Default values
Label
See note (**)
Enablement
Enabled
LED blink
On
Activation unit (where
applicable)
Off
Act as SC1 (where
applicable)
Off
Input Channels
Default values
Enablement
Enabled
Channel label
See note (**)
Trigger zone #1
Address related
See Zone assignment
Operating mode
Style C, NO
Use zone setting
Yes
Output Channels
Default values
Enablement
Enabled
Channel label
See note (**)
Trigger zone #1
Address related
See Zone assignment
Trigger zone #2
None
Trigger zone #3
(where applicable)
None
Trigger zone #4
(where applicable)
None
Trigger point #1
None
Trigger point #2
None
Trigger point #3
None
Silenceable
Yes
Active on disablement
(where applicable)
Off
Trigger on event
Zone Alarm
Delay from alarm
Off
Silenceable
Yes
Sounder pattern
(where applicable)
7Hz fast sweep
Sounder volume
(where applicable)
High Beacon
Enablement (where
applicable)
Enabled
Beacon flash rate
(where applicable)
0.5Hz
DDM module
Default values
Label
See note (**)

Table of Contents