62
Directly to the ceiling
FC490ST Loop service tool
The FC490ST loop service tool is used to program the
loop address into FC addressable devices. The FC490ST
displays information and performs tests on devices. It has
a 32 character backlit LCD alphanumeric display,
arranged in 2 rows of 16 characters and four soft keys,
F1, F2, F3, and F4. Power for the FC490ST is derived
from 4 AA size nickel metal hydride rechargeable
batteries. You can also run it from an unregulated +12
VDC input. Examples include a car cigarette lighter
connection or a 110 230 VAC mains adaptor which will
also recharge the batteries.
FC410CIM Contact input module
The FC410CIM FC addressable contact input module is
designed to monitor fire contacts such as extinguishing
system control, ventilation control, or fire door control etc.
The FC410CIM can be configured as:
Two spur circuits (Class B) monitoring multiple
normally open contacts, with short circuit giving a fault
output
Two spur circuits (Class B) monitoring single normally
closed contacts, with short circuit giving a fault output
Two spur circuits (Class B) monitoring multiple
normally open contacts, with short circuit giving an
alarm
FC410DIM Detector input module
The addressable FC410DIM provides the ability to
connect and Interface one or two zones of 24 VDC 2-wire
conventional detectors (non-addressable) to the fire
alarm controller.
The FC410DIM monitors the status of detectors and
wiring to detectors and signals detector and wiring status
back to the controller.
FC410RIM Relay interface module
The FC410RIM relay interface module provides one volt-
free relay changeover contact on a latching relay. The
relay is controlled by a command sent from the FC fire
controller through the addressable loop. The relay state
(activated, deactivated, or stuck) is returned to the
controller.
FC410BDM Beam detector module
The FC410BDM Beam Detector Interface Module is
designed to interface FIRERAY 50 Beam Detectors to
the FC Digital Addressable Loop. It cannot be used with
other types of beam detectors. The FC410BDM monitors
the Fire and Fault contacts and monitors for open and
short circuits on the connections between the interface
and the beam detector. For remote siting of the FIRERAY
50 an optional BTM800 terminal module can be used with
4 core cable.
The FIRERAY 50 transmitter and receiver units are
mounted in the same housing.
The FC410BDM loop powered beam detector interface
module is contained on a double sided printed circuit
board (PCB) which is fitted into a custom built fascia
plate with a protective cover being fitted over the PCB,
leaving only the connection terminals exposed. The
fascia plate is then fitted onto a standard dual-gang
back box with BESA fittings.
FC400CH Addressable carbon
monoxide + heat detector
The FC400CH carbon monoxide plus heat detector forms
part of the FC400 series addressable fire detectors.
The detector is intended to plug into the following bases:
5B 5” universal base
FC450IB 5” isolator base
FC430SB low power sounder base
FC430LPSB loop powered addressable sounder
base
FC430LPASB loop powered addressable sounder
beacon base
The detector is designed to transmit, to a remote
FireClass controller, digital signals which represent status
of the carbon monoxide and heat elements of the
detector. Software within the controller is used to
interpret the returned carbon monoxide and heat values
to raise alarm or other appropriate response according to
the type of detector configured in the FireClass FC500
(FC501_FC503_FC506) Console.
801RIL Remote LED Indicator
The 801RIL remote indicator is used where a detector
LED is not visible. For example, when the detector is
mounted in a roof void or lift shaft. The 801RIL is
mounted to a single gang electrical box and is supplied
with 2 x M3.5 screws.
801HL Remote LED indicator
The 801HL remote indicator is used where a detector
LED is not visible. For example, when the detector is
mounted in a roof void or lift shaft.
The 801HL provides a larger indicator for use in place of
the 801RIL when longer distances are involved or in VdS
influenced markets.
The 801HL can be mounted to any suitable flat surface
and has fixing centres at 60 mm and 80 mm.
HVR800 High voltage relay
The HVR800 high voltage relay interface is a non-
addressable multi-voltage relay module (operating from
24 VDC, 24 VAC, 120 VAC, and 240 VAC). The
encapsulated HVR800 provides a 10 amp volt-free
contact that can be used to extend the contact ratings
of FC410RIM Addressable Relay Module applications.
If all HVR800s are powered by 120 VAC or 240 VAC, a
maximum of four HVR800s can be individually driven
and controlled by an FC410MIO small addressable
multi-input and output module. For AC operation, no
external DC power supply unit is required to operate the