60
Accessories
The following is a list of accessories for FC503 and
FC506 control panels with a description of the main
features. For further information about these accessories,
refer to the instructions supplied with the accessories or
download them from the FireClass website:
http://www.fireclass.net
FC500IP IP module
The FC500IP is an IP module which is used to connect the
FC503 or FC506 fire panel to a LAN.
The IP Module may be connected to a LAN using a
private IP address or a DHCP address.
The same procedures may be performed using the FireClass
FC500 (FC501_FC503_FC506) Console application, either
through the serial port or the network. With a public IP
address and access to the internet, you can manage and
monitor the control panel from anywhere in the world.
4B Universal base
The 4B Universal base is for use with the FC460, FC400,
and FC600 series of detectors.
The base may be fixed directly to:
British (fixing centers 50 mm) or European (fixing
centers 70 mm) conduit box
4B EM Euro Mounting Box
The suspended ceiling, through the CTA adapter
Directly to the ceiling
FC460H or FC400H Addressable heat
detector
The FC460H or FC400H detector is intended to plug into the
following:
4B 4” Universal Base
4B-I 4” Isolator Base
FC430SB Low Power Sounder Base
FC430LPSB Loop Powered Addressable Sounder Base
FC430LPASB Loop Powered Addressable
Sounder/Beacon Base.
Software within the controller is used to interpret the returned
heat values to raise an alarm or other appropriate responses
according to the type of detector configured in the FireClass
FC500 (FC501_FC503_FC506) Console. The mode of the
detector may be:
EN54-5 A1R, rate-of-rise normal ambient
EN54-5 A2S, fixed 60°C
EN54-5 CR, rate-of-rise high ambient
FC460P or FC400P Addressable optical
smoke
The FC460P and FC400P optical smoke detectors form part
of the FC460 and FC400 series addressable fire detectors.
4BI 4” Isolator base
4B 4” Universal base
FC430SB Low power sounder base
FC430LPSB Loop powered addressable sounder base
FC430LPASB Loop powered addressable sounder
beacon base.
Software within the controller is used to interpret the
returned optical and heat values to raise an alarm or
other appropriate response according to the type of
detector configured in the FireClass FC500
(FC501_FC503_FC506) Console.
FC460PH or FC400PH Addressable optical
smoke & heat detector
The detector is intended to plug into one of the
following:
4B 4” Universal base
4B-I 4” Isolator base
FC430SB Low power sounder base
FC430LPSB Loop powered addressable sounder base
FC430LPASB Loop powered addressable
sounder/beacon base
Software within the controller is used to interpret the re-
turned optical and heat values to raise an alarm or other
appropriate response according to the type of detector
configured in the FireClass FC500
(FC501_FC503_FC506) Console. The mode of detector
may be:
Optical smoke only detector (sensitivity high, normal,
or low)
Optical (sensitivity high, normal, or low) and heat fixed
temperature 60°C (A2S)
Heat only rate-of-rise (A1R) detector (no sensitivity
selection)
Heat fixed temperature 60°C (A2S) (no sensitivity
selection)
Heat rate-of-rise (A1R) detector and optical smoke
(sensitivity high, normal, or low)
HPO (Advanced) smoke detector (sensitivity high,
normal, or low)
HPO Enhanced with heat fixed temperature 60°C
(A2S)
HPO Enhanced rate-of-rise (A1R).
FC460PC Addressable optical smoke &
heat detector & CO
The high performance FC460PC detector detects smoke,
temperature, and CO. It can accurately determine the
presence of all types of fires and has an exceptional
immunity to false alarms.
The functionalities of the FC460PC detector are:
Self-monitoring, self-testing, status indicator, remote
LED, and threshold compensation. FC460PC is
compatible with the existing bases.

Table of Contents

Other manuals for FireClass FC503

Related product manuals