ZN ZT P RC IN: L
10 03 1 3C RF: 1 s
Ê The summary screen for the zone will appear. Note that an "s"
indicates that a serial number has, in fact, been enrolled. The cursor
will be flashing above the loop number. Press [
✱
] to accept the zone
information.
NOTE: If you entered Ò0Ó in the "LEARN S/N?" prompt previously,
you will not get an indication that the serial number has been
enrolled.
If you want to delete the serial number, enter "0" and press [
✱
]. The
system will then prompt, "DELETE S/N?" Press the "1" (YES) key to
complete the delete sequence. This process deletes the serial number
only, not the loop number. The assumption is that the proper loop
number was programmed, but the wrong serial or loop number was
enrolled. To change the loop number, you must go back through zone
programming for that zone and manually enter the loop number over
the existing one.
PROGRAM ALPHA?
0 = NO 1 = YES 0
ENTER ZN NUM.
(00 = QUIT) 11
If you want to program alpha descriptors now, enter "1" (YES). See
the ALPHA DESCRIPTOR PROGRAMMING section for more
information.
If not, enter "0" (NO).
This will return you to the ENTER ZN NUM. prompt for the next
zone. When all zones have been programmed, enter Ò00Ó to quit.
If you plan to enroll serial numbers in the sequential mode, enter Ò00Ó
to quit, then go to the SEQUENTIAL MODE section later in this
manual to enroll the serial numbers.
When you have finished programming all zones (including all serial
numbers), test each zone using the system's TEST mode. Do not use the
Transmitter ID Sniffer mode for this, as it will only check for
transmission of one zone on a particular transmitter, and NOT the zones
assigned to each additional loop.