–84–
¥ When one button of a transmitter (RF, UR, or BR) is activated, all
zones assigned to other buttons on that transmitter are cleared. This
also applies to 5816 and 5817 transmitters which have multiple loops
(zones).
¥ Any transmitter that is not ÒenrolledÓ will not turn off its zone number.
Exit this mode by keying Installer code + OFF.
b. GO/NO GO TEST MODE: ÊÊBy pressing Installer code + # + 4 on
partition 1's keypad, a mode similar to the user test mode (code +
TEST) is entered, but the wireless receiver gain is reduced. Checking in
this mode assists in determining good mounting locations for the
transmitters when the system is being installed and verifies that the RF
transmission has sufficient signal amplitude margin for the installed
system.
Exit the mode by entering Installer code + OFF.
NOTE: System Test Mode (code + test) will be automatically terminated
after 4 hours if the installer or user does not manually terminate it.
This insures that Fire and Panic zones will not remain disabled.
However, Sniffer Mode (installer code + # + 3) does not automatically
expire. You must manually exit (installer code + OFF) sniffer mode to return
to normal operation. Sniffer Mode also terminates if a user arms the system.
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing
by the user are vital to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular
maintenance program to the user as well as acquainting the user with the proper operation
and limitations of the alarm system and its component parts. Recommendations must be
included for a specific program of frequent testing (at least weekly) to insure the system's
proper operation at all times.