Section 26. SPECIFICATIONS &
ACCESSORIES
Specifications
FA162C
SECURITY
CONTROL
1. Physical: 12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x 76mm)
2. Electrical:
VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No.
1321 (in U.S.A.)
RECHARGEABLE BACK-UP BATTERY: 12VDC, 4AH (Gel type).
Charging Voltage: 13.8VDC.
ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or can
drive one or two 702 (series connected) self-contained 20-watt sirens. Do
not connect two 702s in parallel.
AUXILIARY POWER OUTPUT: 12VDC, 600mA max. Interrupts for 4-
wire smoke detector reset.
Note: For UL installations, Alarm Sounder plus Auxiliary Power
currents should not exceed 700mA total.
STANDBY TIME: (see Table in POWERING THE SYSTEM section)
FUSE: Battery (3A) No. 90Ð12
3. Communication:
FORMATS SUPPORTED:
Ademco Express,
10 characters/sec, DTMF (TouchTone) Data Tones, 1400/2300Hz ACK,
1400Hz KISSOFF.
Ademco Contact ID Reporting,
10 characters/sec., DTMF (TouchTone) Data Tones, 1400/2300Hz ACK,
1400Hz KISSOFF.
Ademco Low Speed, 10 pulses/sec, 1900Hz Data Tone,
1400Hz ACK/KISSOFF.
Radionics/SESCOA, 20 pulses/sec, 1800Hz Data Tone, 2300Hz
ACK/KISSOFF. Can report 0Ð9, BÐF
Line Seize: Double Pole
Ringer Equivalence: 0.7B
FCC Registration No.: AC 398UÐ68192ÐALÐE
4. Maximum Zone Resistance: Zones 1Ð8 = 300 ohms excluding EOLR
FA210KP
REMOTE KEYPAD
1. Physical: 5-3/4" W x 4-3/4" H x 1" D (146mm x 121mm x 26mm)
2. Electrical: Voltage Input: 12VDC; Current Drain: 30mA
FA250KP
REMOTE KEYPAD
1. Physical: 5-1/16" W x 6-3/8" H x 1-3/4" D (129mm x 162mm x 45mm)
2. Electrical: Voltage Input: 12VDC; Current Drain: 120mA
FA450KP/FA550KP
REMOTE KEYPADS
1. Physical: 5-1/16" W x 6-3/8" H x 1-3/4" D (129mm x 162mm x 45mm)
2. Electrical: Voltage Input: 12VDC; Current Drain: 140mA

Table of Contents

Other manuals for First Alert FA162C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the First Alert FA162C and is the answer not in the manual?

First Alert FA162C Specifications

General IconGeneral
BrandFirst Alert
ModelFA162C
CategorySecurity System
LanguageEnglish

Related product manuals