Instruction Manual
D103412X012
Detailed Setup—Transducer Block
July 2013
102
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
PD Detail 5 Active
PD_DETAIL5_ACTIVE
74.13 RO
(1)
ALL
0: Relay Disengaged
1: Insufficient Pressure
Differential
2: Travel Calibration Error
3: Reserved
4: High Supply Pressure*
5: Reserved
6: Near a Travel Cutoff Or
Stop
7:Reserved
8: Spec Sheet Fields
Incomplete*
9: Sensor Failure*
10: Pressure Control
Active
11: Transducer Block
Mode OOS
12: Not Authorized for PD
13: PD Run Disabled*
14: Trigger Data
Available*
All bits: 0 N/A
Data Type: Bit String (4 byte)
0=inactive
1=active
Performance Diagnostic Detail
status
*Bits which, when set, will trigger
PERF_ACTIVE bit 2.
PD Detail 6 Active
PD_DETAIL6_ACTIVE
74.14 RO
(1)
ALL Reserved All bits: 0 N/A
Data Type: Bit String (4 byte)
0=inactive
1=active
Performance Diagnostic Detail
status
Shutdown Alerts
SHUTDOWN_ALERTS_ACTIVE
74.15 RO N/A
0: Drive Current
1: Program Memory
2: Static Memory
3: Processor or I/O
Processor
4: Travel Sensor
5: Port A Pressure Sensor
6: Output Block Timeout
7-31: (Reserved)
All bits: 0 N/A
Data Type: Bit String (4 byte)
0=inactive
1=active
Indicates what caused an Instrument
Shutdown. Bit remains set even if
condition has passed if Shutdown
Recovery is Manual. All bits are
cleared when MODE_BLK.TARGET is
written. Always enabled whenever
the corresponding
SHUTDOWN_TRIGGER is enabled.
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-