Table 4‐72. Discrete Output Function Block Parameter Definitions (Continued)
DescriptionInitial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
I/O Options
IO_OPTS
14 OOS
Valid Bits
0: Invert
1: SP tracks PV in Man
3: SP tracks PV in LO
4: SP Track retained
target in Man or LO
6: Fault State to value
0: freeze
1: go to Fault State
value
7: Use Fault State value
on restart
8: Target to Man if Fault
State activated
9: Use PV for
BKCAL_OUT
0: SP
1: PV
All bits: 0
Data Type: Bit String
0=Disable
1=Enable
Allows you to select the type of tracking and the
output value when a fault condition occurs.
Supported I/O options for the DO function block are
SP Tracks PV in Man, SP Tracks PV in LO, SP Tracks
Retained Target in Man or LO, Fault State to Value,
Use Fault state on Restart, Target to Man if Fault
State Activated, and Use PV for BKCAL_OUT.
Status Options
STATUS_OPTS
15 OOS
4: Propagate Failure
Backward
All bits: 0
Data Type: Bit String
0=Disable
1=Enable
Options the user may select for the block processing
of status.
Readback Discrete
READBACK_D
16 RO N/A Dynamic
Data Type: DS‐66
0=closed, 1=open, 5, 10, 15, 30...etc. are position in
5% increments.
Cascade Input Discrete
CAS_IN_D
17 ALL
Status
BAD:
NC:
const
Data Type: DS‐66
The remote set point value from another block.
Value 0
DO Channel
CHANNEL
18 OOS
0=undefined
22=Setpoint (D)
22=
Setpoint (D)
Data Type: Unsigned16
Defines which transducer parameter receives the
DO output. Select Setpoint (D) to control valve
position.
Fault State Time
FSTATE_TIME
19 ALL Positive 0
Data Type: Float
Time from detection of a fault in the remote set
point to the Fault State output action.
Fault State Value Discrete
FSTATE_VAL_D
20 ALL 0
Date Type: Unsigned8
Preset discrete SP_D value to use if I/O_OPTS Fault
State to Value is set.
Back Calculation Output Discrete
BKCAL_OUT_D
21 RO N/A Dynamic
Data Type: DS‐66
The value and status required by the BKCAL_IN_D
input of another block for output tracking
Remote Cascade Input Discrete
RCAS_IN_D
22 ALL
Status
BAD:
NoCom:
NoVal:
const
Date Type: DS‐66
Target set point and status provided by a
supervisory host to a discrete control or output
block.
Value 0