Detailed Setup—DI Function Block
July 2013
202
Modes
The Discrete Input function block supports the following modes:
Manual (Man)—The block output (OUT_D [8]) is disconnected from the field and set manually.
Automatic (Auto)—The block algorithm determines output.
Out of Service (OOS)—The block is not processed. The OUT_D [8] status is set to Bad: Out of Service. The
BLOCK_ERR [6] parameter shows Out of Service.
Block Initialization
The Fieldbus Foundation specification requires that certain parameters in the function blocks have initial values of
uninitialized. In addition to setting the Resource block mode to AUTO, the control system or the user must change
those parameters from their uninitialized value to a valid value in order for the function block to move from the Out of
Service mode. For the DI function block, the CHANNEL [15] parameter must be initialized.
Status Handling
Under normal conditions, a Good: Non‐Cascade status is passed through to OUT_D [8]. The block also supports the
Status Action On Failure and BLOCK_ERR [6] indications.
When SIMULATE_D [9] is enabled, FIELD_VAL_D [7], PV_D [7], and OUT_D [8] change to the simulated status. When
the block is set to Manual mode, OUT_D [7] is set to Good: Non-cascade, Constant status.
I/O Selection
To select the I/O associated with the discrete measurement, configure the value of the CHANNEL [15] parameter.
In the digital valve controller, the four classes of channels are
 Valve travel
 Open/Closed limit switch
 Variable limit switch based on transducer block travel alarm settings.
 Proximity position detection based on transducer block travel alarm settings.
The CHANNEL [15] parameter for each of the four DI blocks available in the digital valve controller may be set
independently to achieve the desired position detection. The DI block CHANNEL [15] definitions are listed in table
4‐77. Refer to the following descriptions for details of the operation of these channels.
Valve Travel
Channel 23 provides valve travel.
0 = Closed, 1 = 100% open, 5 = 5% open, 10 = 10% open, 15 = 15% open, etc.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC6200f and is the answer not in the manual?

Fisher FIELDVUE DVC6200f Specifications

General IconGeneral
BrandFisher
ModelFIELDVUE DVC6200f
CategoryController
LanguageEnglish

Related product manuals