Detailed Setup—Transducer Block
July 2013
90
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
SETPOINT_D
32
Data Type: DS_66
SETPOINT_D is not updated unless
the DO block is selected in
FEATURE_SEL.
STATUS indicates the validity of
value, set by the DO block
OUT.STATUS
VALUE is the discrete value of
setpoint. Only values of 0, 1, or
increments of 5 up to 95 are
allowed. Written by DO channel 22.
Setpoint(D) Status
STATUS
32.1 RW
MAN
OOS
NONE
Setpoint(D)
VALUE
32.2 RW
MAN
OOS
0 = closed 1 = open
5,10,15.. = %
NONE
TRAVEL_D
33
Data Type: DS_66
STATUS indicates the validity of
VALUE.
VALUE: 0=closed , 1=open
5,10,15.. = %. Controls DI Channel
23
Travel(D) Status
STATUS
33.1 RO N/A N/A
Travel (D)
VALUE
33.2 RO N/A
0 = closed 1 = open
5,10,15.. = %
N/A
TRAVEL
34
Data Type: DS‐65
In Travel Control:
Actual valve travel
in % of calibrated travel range.
In Pressure Control:
Implied valve
travel in % of pressure range.
Controls AI channel 4.
Travel Status
STATUS
34.1 RO N/A N/A
Travel
VALUE
34.2 RO N/A N/A
SUPPLY_PRESSURE
35
Data Type: DS‐65
STATUS indicates the validity of
VALUE. VALUE is pressure of air
supply, controls AI channel 5.
Supply Pressure Status
STATUS
35.1 RO N/A N/A
Supply Pressure
VALUE
35.2 RO N/A N/A
PRESSURE_A
36
Data Type: DS‐65
STATUS Indicates the validity of
VALUE.
Pressure of primary air output,
controls AI channel 6.
Pressure A Status
STATUS
36.1 RO N/A N/A
Pressure A
VALUE
36.2 RO N/A N/A
PRESSURE_B
37
Data Type: DS‐65
STATUS indicates the validity of
VALUE. VALUE is the
Pressure on secondary output,
controls AI channel 7.
Pressure B Status
STATUS
37.1 RO N/A N/A
Pressure B
VALUE
37.2 RO N/A N/A
-Continued-