Loading...
15 Outputs (TF7-*72***-******-******a-*****-**; a = M, P, Q)
15.1 Configuration of a digital output as binary output FLUXUS H721
2022-05-15, UMFLUXUS_H721V1-5EN
154
15 Outputs (TF7-*72***-******-******a-*****-**; a = M, P, Q)
If the transmitter is equipped with outputs, they have to be
configured. For the configuration of the analog output, see
section 9.3.6.
The transmitter can also be equipped with digital outputs. A
digital output combines the functions of the following
outputs:
binary output (output of binary switching conditions)
pulse output (integrating output of quantities)
frequency output (scaled output of flow quantities)
These functions depend on the selected physical quantity.
15.1 Configuration of a digital output as binary output
A digital output switches if one of the following switching conditions is met:
the measured value exceeds or falls below a limit
the measured value lays within or outside a defined range
a measurement is not possible
an event occurs
Assignment of an output
Select the channel in the program branch Options (here: Channel A).
Press ENTER.
This display will not be indicated if the transmitter has only one measuring channel.
Select the list item Outputs.
Press ENTER.
Select an output to be assigned to the channel (here: Digital output B1).
Press ENTER.
If the output has already been assigned to a channel, it is displayed as follows: Digital output B1 (A).
Options
Channel x
Outputs
Select output
Enable output
Source item
see annex A
Tab. 15.1: Output via digital outputs
source item binary output pulse output frequency output
status value event value
physical
quantities
Sound speed xx
Flow quantities xx
Totalizers xx
Pulse x
Fluid properties xx
Diagnostic values x
Miscellaneous
(Custom. Input 1...4)
xx
events Event trigger x
Options\Channel A
Options\Channel A\Outputs\Digital output B1(--)