Example 3
The flow velocity is measured.
If the flow velocity is ≤ 5 m/s, the transmitter measures in the TransitTime mode. As long as the flow velocity is > 5 m/s, the
transmitter has to measure in the FastFood mode.
Trigger:
Condition:
Action:
flow velocity > 5 m/s
R1 with flow velocity > 5 m/s
measurement in the FastFood mode
Options Options
Event trigger Remote functions
Select R1 Enable FastFood
→ R1
Enable R1
Yes
Source item
→ Flow quantities
Flow quantities
→ Flow velocity
Function
→ MAX (x>limit)
Type
→ Non-hold
Trigger value
→ 5 m/s
Hysteresis
→ 0.4 m/s
Glitch interval
→ 1.0 s
Failure delay
→ 1.0 s