HF2211 Serial Server Device User Manual
http://www.iotworkshop.com - 54 -
Disable: disable software flow control function. Default: Disable.
4.2.1.28. UART/Cli-Getin Command
Function: Display/Set Cli command function
Format:
Query
<Cli-Getin>
Set
<Cli-Getin> [Serial-String/Always/Disable]
Parameter:
Set Cli command parameters. Setting is valid immediately.
Serial-String: Enable specific data to enter into Cli command mode.
[Input Serail String]: Default: +++, Range1~10 bytes. Also can input hex
format data. The HEX data are separated by Spaces, Like【30 31 32 33 34】,
When it recieved string data “01234”, then It can enter into Cli command.
Always: Always work in Cli command mode when device power on.
Disable: Disable Cli command mode. UART and Telnet both can’t use Cli
Command.
4.2.1.29. UART/Cli-WaitTime Command
Function: Display/Set Cli command wait time
Format
<Cli-WaitTime>
Set
<Cli-WaitTime> [timeout]
Parameter:
Set Cli command mode timeout exit time. If there is no Cli command sent for the
waitfime, It will exit Cli command mode to transparent transmission, Setting is valid
immediately.
timeout: Default: 300s, Range 0: Disable WaitTime function, 1~300s.
4.2.1.30. UART/Proto command
Function: Display/Set UART protocol function
Format:
Query
<Proto>
Set
<Proto> [NONE/Modbus/Frame]
Parameter:
Setting is valid immediately.
NONE: Default: None, transparent transmission, the received UART data will be
directly sent to network.
Modbus: Modbus RTU to Modbus TCP.