FLIRCM85USERMANUALDocumentIdentifier:CM85‐en‐US_AB
19
5.8PowerMeasurements
5.8.1SinglePhasePowerMeasurements
1. SetthefunctionswitchtotheWposition.
2.
InserttheblackprobeleadintothenegativeCOMterminalandtheredprobeleadinto
thepositiveWterminal.
3.
Pressthetriggertoopentheclampjaws.Fullyencloseoneconductor—refertoFigure5.1.
Foroptimumresults,centertheconductorinthejaws.
Note:The+symbolonthejawshouldbedirectedtowardthepowersource
4. Connecttheprobeleadsinparalleltothepartundertest.
5.
Readtheactivepowervalueonthedisplay.
Ifthevalueisdisplayedwithoutasign,thepowerisflowingfromthepowersourceto
theload.
Ifthevalueisdisplayedwithaminussign(–),thepowerisflowingfromthepowerload
tothesource.
6. Tomeasureanddisplaythepowerfactor,press
theMODEbuttonrepeatedlyuntilthe
indicatorisdisplayed.
7. Readthepowerfactorvalueonthedisplay.
Ifthevalueisdisplayedwithoutasign,thephaseofthecurrentsignalislaggingbehind
thevoltagesignal(inductiveload).
Ifthevalueisdisplayedwithaminussign(–),thephaseofthecurrentsignalisleading
thevoltagesignal(capacitiveload).
8. Toreturntoactivepowermeasurements,presstheMODEbuttonrepeatedlyuntilneither
the
northe indicatorisdisplayed.
Ifanoverloadoccurs,thefollowingisdisplayed:
OL.V:Voltageoverloadorbothvoltageandcurrentoverload.
OL.A:Currentoverload.
OL.kW:Activepoweroverload.