5.8.2Three‐PhasePowerMeasurements
5.8.2.1Three‐PhaseThree‐WireBalanced/Unbalanced
Thepowerofathree‐phasethree‐wiredeltaconfigurationismeasuredintwosteps,in
accordancewithFigure5.4.Thetotalpoweristhesumofthetwomeasurements:W=W
1
+W
2
.
Figure5.4Three‐phasethree‐wiremeasurements
1. SetthefunctionswitchtotheWposition.
2.
Ensurethatthemeterissettoactivepowermeasurement.Ifthe orthe
indicatorisdisplayed,presstheMODEbuttonrepeatedlyuntilnoneofthese
indicatorsaredisplayed.
3.
Taketwomeasurementsoftheactivepower,inaccordancewithFigure5.4.
4.
Tomeasureanddisplaythepowerfactor,presstheMODEbuttonrepeatedlyuntilthe
indicatorisdisplayed.
5.
Readthepowerfactorvalueonthedisplay.
Ifthevalueisdisplayedwithoutasign,thephaseofthecurrentsignalislagging
behindthevoltagesignal(inductiveload).
Ifthevalueisdisplayedwithaminussign(–),thephaseofthecurrentsignalis
leadingthevoltagesignal(capacitiveload).
6. Toreturntoactivepowermeasurements,presstheMODEbuttonrepeatedlyuntil
neitherthe
northe indicatorisdisplayed.