EasyManuals Logo

Fluidwell F012-P User Manual

Fluidwell F012-P
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
F012-P User Manual
FW_F012-P_M_v0501-01_EN Page 13
5.3 SETUP MENU OVERVIEW
1 TOTAL DEFAULT
1.1 UNIT
L - m3 - kg - lb - GAL - USGAL - bbl - no unit L
1.2 DECIMALS
0 - 3 0
1.3 K-FACTOR
0.000010 - 9,999,999 1
1.4 DECIMALS K-FACTOR
0 - 6 0
2 FLOW RATE DEFAULT
2.1 UNIT
mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV -
no unit - scf - Nm3 - NL - P
L
2.2 TIME UNIT
sec - min - hour - day min
2.3 DECIMALS
0 - 3 0
2.4 K-FACTOR
0.000010 - 9,999,999 1
2.5 DECIMALS K-FACTOR
0 - 6 0
2.6 CALCULATION
per 1 - 255 pulses 10
2.7 CUT-OFF
0.1 - 999.9 seconds 30
3 DISPLAY DEFAULT
3.1 FUNCTION
total - flow rate total
3.2 BACKLIGHT
off - on off
3.3 BACKLIGHT
BRIGHTNESS
1 - 5 5
4 POWER MANAGEMENT DEFAULT
4.1 LCD UPDATE
fast - 1 sec - 3 sec - 15 sec - 30 sec - off 1 sec
4.2 BATTERY MODE
operational - shelf operational
5 FLOWMETER DEFAULT
5.1 SIGNAL
npn - npn_lp - reed - reed_lp - pnp - pnp_lp - namur -
coil_hi - coil_lo - active
coil_lo
6 OTHERS DEFAULT
6.1 TYPE / MODEL
fixed F012-P
6.2 SOFTWARE VERSION
fixed 03.xx.xx
6.3 SERIAL NUMBER
fixed xxxxxxx
6.4 PASS CODE
0000 - 9999 0000
6.5 TAG NUMBER
0000000 - 9999999 0000000
5.4 SETUP MENU EXPLANATIONS
5.4.1 MENU 1: TOTAL
Calculating the K-factor for Total
The K-factor is used to convert the flowmeter pulse frequency to a quantity. Two examples are
given.
Example 1
The flowmeter generates 2.4813 pulses per liter.
The flow will be displayed using cubic meters (m3; 1.1: TOTAL > UNIT).
A cubic meter equals 1000 liters, thus the flowmeter generates 2,481.3 pulses per m3.
Enter the K-factor as 248130 at 1.3: TOTAL > K-FACTOR and 2 at 1.4: TOTAL > DECIMALS K-FACTOR.
Example 2
The flowmeter generates 6.5231 pulses per gallon.
The flow will be displayed using gallons (1.1: TOTAL > UNIT).
Enter the K-factor as 652310 at 1.3: TOTAL > K-FACTOR and 5 at 1.4: TOTAL > DECIMALS K-FACTOR.

Table of Contents

Other manuals for Fluidwell F012-P