100
Fault Cause
Remedy
Bypass
CommunicationsError
Bypasscommunicationerror
occurswhentheBypassand
I/Oboardlosesthe
connectionbetweenthem.
Checktheconnectionbetweenthe
BypassboardandtheI/Oboard,
thattheconnectorisfirmandthatit
isinthecorrectsocket.
Alsocheckconditionofwirethat
therearenoinsolationissuesalong
it’slength.
BypassContactor ABypassContactortrip
occurswhenthereisanissue
withthecontactors.It
usuallyindicatesthateither
motorisdisconnectedor
contactordidn’tpullinor
contactorcoilpullstoomuch
currentandactivated24VDC
poweroverloadprotectionor
itisdisconnected.
Checkthatamotorishookedupto
theconta
ctoroutput.
EnsurecontactorisFCSbrandand
properlysizedforapplication
Checkforcontactorcoilconnection
tobypassboard
Checkforshortsinthecontactorcoil
orinthewiringtothecontactor.
Disconnectcontactorcoilandcheck
voltagecomingfromcontrolboard.
Ifduri
ngbypassrunmodethereis
novoltage,stopbypassandwaitfor
afewminutesforoverloadto
cooldownandcheckagain24VDC
powerduringrunmode.
BypassCurrentat
PowerOn
Bypassmeasuresthecurrent
atpoweronwiththe
contactorsopen,ifthereis
current(>0)thisfaultis
triggered.
Checkforpropermotorwiring
throughtheBypasscurrentsensors.
Checkforcontactorthatislocked
closed.
Checkforpropercalibrationofthe
bypassunit.
BypassNoMotor
Current
Bypassmeasuresthecurrent
wheninrunningstate.If
thereisnomeasuredcurrent
(0)thenthisfaultistriggered.
Checkforpropermotorwiring
throughtheBypasscurrentsensors.
Checkforcontactorthatislocked
open.
Checkforpropercalibrationofthe
bypassunit.
BypassLockedRotor Alockedrotorfaultoccurs
whenduringstartcurrent
exceeds300%oftheFLA
settinganditisnot
decreasingafter0.5seconds.
CheckthatyourFLAsetti ngin
PRIMARY04matchesthemotor
nameplate
Checkifthemotorspinsfreelyorif
motorshaftislocked.
Checkwiringinmotorj
unctionbox.
Checkphasesequenceforproper
rotationdirectionforsystemswith
mechanicallyblockedreverse
rotation.
MonitorPF(PowerFactor)reading
atstart.Ifitislessthan0.2and
doesnotchange,calltechsupport
tocheckwiring.

Table of Contents