44
Code
Modbus
Address
FullParameterName
OLEDDisplay
Name
ParameterSettingRange
Adj.During
43 143 ReferenceLossCondition AnlgRefLoss 0‐Disabled
1‐Below1/2ofMin
2‐BelowMin
No
44 144 Ref.LossAction AnlgRefLossAct 0‐Fault
1‐Stop(usesselected
stopmode)
2‐HoldSpeed
No
45 145 Ref.LossDelay AnlgRefLoss 0to20[Sec] No
46 146 PIDModeSelect PIDMode 0‐Direct
1‐Inverse
No
47 147 PIDSetpointSource SetpointSource 0‐Keypad
1‐1AAnalogInput
2‐2AAnalogInput
3‐Comms
4‐3AInput
No
48 148 PIDFeedbackSource FeedbackSource 0‐1AInput
1‐2AInput
2‐3AInput
No
49 149 PIDFeedbackUnit FeedbackUnits 0–PSI(0.1)
1–GPM(0.1)
2–inWC(0.01)
3–CFM(0.1)
4–inHg(0.1)
5–Feet(0.1)
6‐°F(0.1)
7–mBar(0.01)
8–Pa(0.1)
9–kPa(0.01)
10–Meters(0.1)
11‐°C(0.1)
12–Custom(0.1)
13‐%(0.1
)
No
50 150 PIDFeedbackMax FeedbackMax 0.0to6000.0[Unit] No
52 152 PIDSet‐pointvalue KeypadSetpoint 0.0to95%of[PIDF/B
Max]
No
55 155 PIDP‐Gain PGain 0to999[%] Yes
56 156 PIDI‐Gain IGain 0.1to32.0[Sec] Yes
57 157 PIDOutRampTime PIDRampTime 0.0to10.0[Sec] Yes
58 158 PIDHighFrequencyLimit PIDHighFreq
Limit
[Prime‐59]to[Prime‐07]
[Hz]
No
59 159 PIDLowFrequencyLimit PIDLowFreqLimit 0.00to[Prime‐58][Hz] Yes
60 160 FeedbackSignalLoss FdbkLoss 0‐Disabled
1‐Below1/2ofMin
2‐BelowMin
No