S90-010 M FRICK
QUANTUM™ COMPRESSOR CONTROL PANEL
Page 48 MAINTENANCE
CAPACITY CONTROL SETPOINTS
SUCTION PRESSURE CONTROL MODE #1
setting default range
Capacity Control Setpoint ______ 20 psig 30" - 135 psig
Upper Proportional Band ______ 4 psig 0 - 20 psig
Upper Dead Band ______ 0.5 psig 0 - 10 psig
Upper Cycle Time ______ 3 sec. 0 - 60 sec.
Lower Proportional Band ______ 4 psig 0 - 20 psig
Lower Dead Band ______ 0.5 psig 0 - 10 psig
Lower Cycle Time ______ 3 sec. 0 - 60 sec.
Autocycle Start Pressure ______ 25 psig 30" - 135 psig
Autocycle Start Delay ______ 1 min. 0 - 60 min.
Autocycle Stop Pressure ______ 15 psig 30" - 135 psig
Autocycle Stop Delay ______ 1 min. 0 - 60 min.
Low Suction Pressure Stop Load ______ 10 psig 30" - 135 psig
Low Suction Pressure Force Unload ______ 5 psig 30" - 135 psig
Low Suction Pressure Alarm ______ 2 psig 30" - 135 psig
Low Suction Pressure Alarm Delay ______ 2 sec. 0 - 60 sec.
Low Suction Pressure Shutdown ______ 0 psig 30" - 135 psig
Low Suction Pressure Shutdown Delay ______ 3 sec. 0 - 60 sec.
SUCTION PRESSURE CONTROL MODE #2
setting default range
Capacity Control Setpoint ______ 20 psig 30" - 135 psig
Upper Proportional Band ______ 4 psig 0 - 20 psig
Upper Dead Band ______ 0.5 psig 0 - 10 psig
Upper Cycle Time ______ 3 sec. 0 - 60 sec.
Lower Proportional Band ______ 4 psig 0 - 20 psig
Lower Dead Band ______ 0.5 psig 0 - 10 psig
Lower Cycle Time ______ 3 sec. 0 - 60 sec.
Autocycle Start Pressure ______ 25 psig 30" - 135 psig
Autocycle Start Delay ______ 1 min. 0 - 60 min.
Autocycle Stop Pressure ______ 15 psig 30" - 135 psig
Autocycle Stop Delay ______ 1 min. 0 - 60 min.
Low Suction Pressure Stop Load ______ 10 psig 30" - 135 psig
Low Suction Pressure Force Unload ______ 5 psig 30" - 135 psig
Low Suction Pressure Alarm ______ 2 psig 30" - 135 psig
Low Suction Pressure Alarm Delay ______ 2 sec. 0 - 60 sec.
Low Suction Pressure Shutdown ______ 0 psig 30" - 135 psig
Low Suction Pressure Shutdown Delay ______ 3 sec. 0 - 60 sec.