QUANTUM™ COMPRESSOR CONTROL PANEL S90-010 M
MAINTENANCE Page 49
PROCESS TEMP CONTROL MODE #1
setting default range
Capacity Control Setpoint ______ 40°F -238 - 302°F
Upper Proportional Band ______ 4°F 0 - 20 °F
Upper Dead Band ______ 1°F 0 - 10°F
Upper Cycle Time ______ 4 sec. 0 - 60 sec.
Lower Proportional Band ______ 4°F 0 - 20 °F
Lower Dead Band ______ 1°F 0 - 10°F
Lower Cycle Time ______ 4 sec. 0 - 60 sec.
Autocycle Start Temp ______ 45°F -238 - 302°F
Autocycle Start Delay ______ 1 min. 0 - 60 min.
Autocycle Stop Temp ______ 36°F -238 - 302°F
Autocycle Stop Delay ______ 1 min. 0 - 60 min.
Low Process Temp Stop Load ______ 35°F -238 - 302°F
Low Process Temp Force Unload ______ 34°F -238 - 302°F
Low Process Temp Alarm ______ 33°F -238 - 302°F
Low Process Temp Alarm Delay ______ 3 sec. 0 - 60 sec.
Low Process Temp Shutdown ______ 32°F -238 - 302°F
Low Process Temp Shutdown Delay ______ 3 sec. 0 - 60 sec.
Low Suction Pressure Stop Load ______ 10 psig 30" - 135 psig
Low Suction Pressure Force Unload ______ 5 psig 30" - 135 psig
Low Suction Pressure Alarm ______ 2 psig 30" - 135 psig
Low Suction Pressure Alarm Delay ______ 3 sec. 0 - 60 sec.
Low Suction Pressure Shutdown ______ 0 psig 30" - 135 psig
Low Suction Pressure Shutdown Delay ______ 3 sec. 0 - 60 sec.
PROCESS TEMP CONTROL MODE #2
setting default range
Capacity Control Setpoint ______ 40°F -238 - 302°F
Upper Proportional Band ______ 4°F 0 - 20 °F
Upper Dead Band ______ 1°F 0 - 10°F
Upper Cycle Time ______ 4 sec. 0 - 60 sec.
Lower Proportional Band ______ 4°F 0 - 20 °F
Lower Dead Band ______ 1°F 0 - 10°F
Lower Cycle Time ______ 4 sec. 0 - 60 sec.
Autocycle Start Temp ______ 45°F -238 - 302°F
Autocycle Start Delay ______ 1 min. 0 - 60 min.
Autocycle Stop Temp ______ 36°F -238 - 302°F
Autocycle Stop Delay ______ 1 min. 0 - 60 min.
Low Process Temp Stop Load ______ 35°F -238 - 302°F
Low Process Temp Force Unload ______ 34°F -238 - 302°F
Low Process Temp Alarm ______ 33°F -238 - 302°F
Low Process Temp Alarm Delay ______ 3 sec. 0 - 60 sec.
Low Process Temp Shutdown ______ 32°F -238 - 302°F
Low Process Temp Shutdown Delay ______ 3 sec. 0 - 60 sec.
Low Suction Pressure Stop Load ______ 10 psig 30" - 135 psig
Low Suction Pressure Force Unload ______ 5 psig 30" - 135 psig
Low Suction Pressure Alarm ______ 2 psig 30" - 135 psig
Low Suction Pressure Alarm Delay ______ 3 sec. 0 - 60 sec.
Low Suction Pressure Shutdown ______ 0 psig 30" - 135 psig
Low Suction Pressure Shutdown Delay ______ 3 sec. 0 - 60 sec.