Parameters overview | 4
B1820023_en | Service handbook Lambdatronic H 3200 - T4e 61
Boiler - General settings - Operator data
System menu Boiler
Operator data
Production number
For unique identification of the boiler on the froeling-
connect server, the facility number listed on the
identification plate must be set here.
Customer number
By setting the customer number, this is automatically
transferred into the commissioning report when it is saved.
Boiler number
By setting the boiler number, this is automatically
transferred into the commissioning report when it is saved.
4.6 Boiler 2
4.6.1 Boiler 2 - Status
Temperature of backup boiler
Displays the current boiler temperature of the backup
boiler.
Burner relay status
Shows the current status of the burner relay:
▪ 0: Backup boiler not active
▪ 1: Backup boiler active
Backup boiler pump
Prerequisite: Set the parameter “Switch valve installed“
to “NO”
Display of the current pump control for the standby boiler.
Standby boiler switch valve
Prerequisite: Set the parameter “Switch valve installed“
to “YES”
Display of the current switch valve control of the standby
boiler.
Manual start of backup boiler (only when the ID fan is
switched off)
▪ OFF: Backup boiler is controlled according to the
program that is set
▪ ON: Backup boiler is activated immediately
NOTICE!Response to burner blockage!
Heat pump mode
If a heat pump is used as a backup boiler, the operating
mode will be displayed here. The operating mode selected
is dependent on the outdoor temperature and flow
temperature.
Heat pump status
Indicates the current status of the control process of the
heat pump.