4 | Parameters overview
64 B1820023_en | Service handbook Lambdatronic H 3200 - T4e
4.8 Feed system
4.8.1 Feed system - Cyclone 1
System menu Discharge
Cyclone 1
Cyclone active
▪ NO: Cyclone on the vacuum discharge system is not in
use.
▪ YES: Cyclone on the vacuum discharge system is in
use.
Active suction system
Prerequisite: 1-2-3 suction module when using up to
three identical discharge systems.
Specifies which discharge system is currently being used.
Active probe
Prerequisite: 1-2-3 suction module in combination with
RS4 / RS8 pellet suction system
Probe of the active discharge system, which is used for
suction.
Cyclone status
Shows the current status of the cyclone.
Status of the vacuum discharge system
Shows the current status of the vacuum discharge system
that feeds the cyclone.
Switch-on delay MIN sensor
Duration after which the suction turbine is activated.
Empty the cyclone completely after how many
filling operations?
Specifies after how many fillings the cyclone is to be
completely emptied.
Maximum time until switching of probe
Prerequisite: Feed system 4 probe switch or 8 probe
switch
Time period, during which the cyclone must reach a fill
level of 100% from a probe. If this time is exceeded, the
change-over unit automatically changes to the next probe.
If all probes are started and the fill level of 100% in the
cyclone is not reached, an error message appears on the
display.
Probe suction reversal for
Prerequisite: RS4 / RS8 pellet suction system
Before switching to the next probe, the probe that was last
used is back-flushed for the time set.
Max. runtime of suction fan
Prerequisite: Feed system bag silo or suction screw
If the 100% fill level in the cyclone has not been reached
within the specified runtime, the suction turbine switches
off.
Vacuum + screw filling run-on after reaching the
MAX fill level
Specifies how long the suction screw should deliver
material after reaching the maximum fill level in the
cyclone. After this runtime, the run-on time of the suction
turbine starts (parameter “Suction run-on”)
Suction run-on
When the fill level sensor detects fuel in the cyclone, the
suction turbine remains active for the time set.
Shaker motor installed
▪ YES: The vibration motor for improving the discharge
rate of the bag silo is installed.
Shaker timing
The default vibration interval timing is 60%:
Time basis: 100 sec. → 60 sec. on / 40 sec. pause
Nominal current for discharge screw
Nominal current of the suction screw motor according to
the identification plate on the motor.
During troubleshooting of suction screw, this
turns backwards for
Duration, how long should the suction screw turn
backwards during troubleshooting.
During troubleshooting of suction screw, this
turns forwards for
Duration, how long should the suction screw turn forwards
during troubleshooting.