4 | Parameters overview
88 B1820023_en | Service handbook Lambdatronic H 3200 - T4e
Switching-type sensor
Setting
Lambda values Switching-type sensor
Residual oxygen content
Display of the current residual oxygen content.
Lambda probe voltage measured
Display of the current measured Lambda probe voltage.
Lambda probe correction value
Correction value for lambda measurement. If too much is
displayed, this value must be set to positive, if too little is
displayed, the value must be set to negative.
Lambda probe voltage corrected
Display of the measured Lambda probe voltage, at which
the „Lambda probe correction value“ governs the
response.
Broadband probe
Setting
Lambda values Broadband probe
Residual oxygen content
Display of the current residual oxygen content.
Broadband probe heating current
The measured heating current of the broadband probe is
displayed.
Broadband probe heating voltage
The measured heating voltage of the broadband probe is
displayed.
Broadband probe Nernst voltage
The measured Nernst voltage of the broadband probe is
displayed.
Broadband probe pump current
The measured pump current of the broadband probe is
displayed.
Broadband probe internal resistance
Display of the measured internal resistance of the
broadband probe.
Pump current at the last calibration