Installation
Assembly work
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 15
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M1020008_en
3
3.2.3 Minimum distances in the boiler room
The boiler should always be set up so that it is fully accessible to
allow fast and easy maintenance.
Observe the applicable standards and regulations when setting up
the boiler.
Also observe the standards pertaining to noise protection
(ÖNORM H 5190 - Noise protection measures)
Dimension
Description Units 70-100
A Minimum distance from back of boiler to wall 700
B Minimum distance from front of boiler to wall
(space required for opening insulating door)
950
C Minimum distance between stoker and wall 300
D Minimum distance from edge of boiler to wall
(space required to empty ashcan)
mm
700
3.2.4 General information for boiler room
Danger of fire due to flammable materials. No flammable materials
should be stored near the boiler.
Damage due to impurities in combustion air.
Do not use any solvents or cleaning agents containing chlorine in the
room where the boiler is installed.
Keep the air suction opening of the boiler free of dust.
The room where the boiler is installed must be frost-proof.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Froling Turbomatic TMC 70 and is the answer not in the manual?

Froling Turbomatic TMC 70 Specifications

General IconGeneral
BrandFroling
ModelTurbomatic TMC 70
CategoryBoiler
LanguageEnglish

Related product manuals