73
EN
DC Mode DC mode
FIX Voltage value in V for fixed voltage operation
User Voltage value in V for MPP User operation
Grid Monitoring:
GMTi Start-up time of inverter in s
GMTr Reconnection time in s following a grid fault
ULL Mean grid voltage over 10 minutes in V.
LL Trip Trip time for long-term voltage monitoring
Voltage Limits:
UIL max Upper inner grid voltage in V
UIL min Lower inner grid voltage in V
UOL max Upper outer grid voltage limit value in V
UOL min Lower outer grid voltage limit value in V
Frequency Limits:
FIL max Upper inner grid frequency in Hz
FIL min Lower inner grid frequency in Hz
FOL max Upper outer grid frequency limit value in Hz
FOL min Lower outer grid frequency limit value in Hz
LVFRT:
Status Status of the LVFRT function (Low Voltage Fault Ride Through,
according to BDEW TR3 5.7)
DB min Dead Band Value min.
Lower voltage limit as % for the reactive power feed
DB max Dead Band Value max.
Upper voltage limit as % for the reactive power feed
k-Fac Gradient showing how much reactive current is fed in as a func-
tion of voltage
P AC Reduction:
Max. P AC Manual power reduction
GPIS Softstart function
GFDPRv Grid frequency-dependent power reduction in %/Hz
GFDPRr Return to nominal output in %/s (following a grid frequency-in-
duced power reduction)