EasyManuals Logo

Fronius Agilo 75.0-3 User Manual

Fronius Agilo 75.0-3
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
92
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
486
- External NO contact is open
- Optional measuring and monitoring relay has tripped
Behaviour The inverter is not feeding any energy into the grid.
Remedy Close external NO contact;
check measuring and monitoring relay
If this status code keeps recurring, contact your system engi-
neer
487
Air inlet temperature sensor is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy Replace air inlet temperature sensor - notify a Fronius-trained
service engineer
488
AC measurement device is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
490, 491
Internal communication error
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
492
DC main switch is switched off
Behaviour The inverter is not feeding any energy into the grid.
Remedy Switch on DC main switch
493
DC relay is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
494
Grounding fault on the control board
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Agilo 75.0-3 and is the answer not in the manual?

Fronius Agilo 75.0-3 Specifications

General IconGeneral
BrandFronius
ModelAgilo 75.0-3
CategoryInverter
LanguageEnglish

Related product manuals