2 Installation and Connection 2-7
FVR-C11S-EN
2
Table 2-3-3 Description of function F02
F02 When SW7 is set at CM When SW7 is set at P24
0
When +24 to +27 VDC is supplied to
FWD - P24/CM, pressin
g
the ke
y
on the
ke
y
pad panel starts forward operation.
When +24 to +27 VDC is supplied to
REV - P24/CM, pressin
g
the ke
y
on the
ke
y
pad panel starts reverse operation.
When +24 to +27 VDC is supplied to both
FWD - P24/CM and REV - P24/CM, the inverter
decelerates to stop.
When FWD is short-circuited to P24/CM and the
ke
y
on the ke
y
pad panel is pressed, for-
ward operation starts.
When REV is short-circuited to P24/CM and the
ke
y
on the ke
y
pad panel is pressed, re-
verse operation starts.
When both FWD - P24/CM and REV - P24/CM
are short-circuited, the inverter decelerates to
stop.
1
When +24 to +27 VDC is supplied to
FWD - P24/CM, forward operation starts.
When +24 to +27 VDC is supplied to
REV - P24/CM, reverse operation starts.
When +24 to +27 VDC is supplied to both
FWD - P24/CM and REV - P24/CM, the inverter
decelerates to stop.
Short-circuit FWD to P24/CM for forward opera-
tion, or REV to P24/CM for reverse operation.
Short-circuitin
g
both FWD - P24/CM and REV -
P24/CM brin
g
s the inverter to deceleration and
stop.
3) Analo
g
input terminal (13, 12, 11, C1)
Use these terminals to connect external input
analo
g
volta
g
e and analo
g
current and fre-
quenc
y
settin
g
device (POT). For connectin
g
a contact to this circuit, use a twin contact for
fine current si
g
nal.
Do not use a contact for terminal 11.
CAUTION
In case P24 is short-circuited with 0V
b
y
outer circuit when SW7 is set to P24
side, pol
y
switch (F1) turns the power
off. To recover the power, open the
short circuit and turn the inverter off to
allow the temperature to lower.
WARNING
The STOP ke
y
is valid onl
y
when the
function has been set. Prepare
another switch for emer
g
enc
y
stop.
When operation usin
g
an external si-
g
nal terminal is selected, the operation
cannot be stopped usin
g
the STOP
ke
y
on the ke
y
pad panel.
Otherwise accidents could occur.