EasyManua.ls Logo

Fuji Electric FVR-C11S-7EN Series - Page 42

Fuji Electric FVR-C11S-7EN Series
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-2 5 Selectin
g
Function
FVR-C11S-EN
5
Chan
g
e durin
g
operation: X = impossible, = possible (enabled b
y
usin
g
), = possible (enabled b
y
usin
g
)
Function
code No.
Name Settin
g
ran
g
e Unit
Min.
unit
Factor
y
settin
g
Chan
g
e
durin
g
opera-
tion
User
settin
g
F10
Electronic
thermal overload
rela
y
for motor
(Select)
0: Inactive
1: Active (for 4-pole standard motor)
2: Active (for 4-pole FUJI inverter motor)
-- 1
F11 (Level) 20 to 135% of inverter rated current A 0.01
T
y
pical
value of
FUJI
4-pole
motor
F12
(Thermal
time
constant)
0.5 to 10.0min min 0.1 5.0
F14
Restart after mo-
mentar
y
power
failure (Select)
0: Inactive (Trip and alarm when power fail-
ure occurs)
1: Inactive (Trip and alarm when power re-
covers)
2: Active (Momentaril
y
stops and restarts at
settin
g
frequenc
y
of before power failure)
3: Active (Momentaril
y
stops and restarts at
startin
g
frequenc
y
)
-- 0 X
F15
Frequenc
y
limiter
(Hi
g
h)
0 to 120Hz
Hz 1
70
F16 (Low) 0 to 120Hz 0
F17
Gain
(for frequenc
y
settin
g
si
g
nal)
0: For 0 to 10VDC (4 to 20 mA DC)
1: For 0 to 5VDC (4 to 12 mA DC)
-- 0 X
F18 Bias frequenc
y
-120 to 120Hz Hz 1 0
F20
DC injection brake
(Startin
g
freq.)
Fixed to 3Hz Hz - 3.0 -
F21 (Level) 0 to 100% % 1 50
F22
(Brakin
g
time)
0.0 s (Inactive), 0.1 to 30.0 s s 0.1 0.0
F23
Startin
g
frequenc
y
1 to 6Hz Hz 1 1 X
F24 - Data cannot be chan
g
ed. - - 0.0 -
F25 Stop frequenc
y
1 to 6Hz Hz 1 1 X

Table of Contents

Related product manuals