5 Selectin
Function 5-3
FVR-C11S-EN
5
Chan
g
e durin
g
operation: X = impossible, = possible (enabled b
y
usin
g
), = possible (enabled b
y
usin
g
)
Func-
tion
code
No.
Name Settin
g
ran
g
e Unit
Min.
unit
Factor
y
settin
g
Chan
g
e
durin
g
opera-
tion
User
set-
tin
g
F26
Motor sound
(carrier freq.)
0 to 15kHz
0.75kHz is set when 0 is specified
kHz 1 15
F27 (sound tone )
0: Level 0 1: Level 1
2: Level 2 3: Level 3
-- 0
F30
FM terminal
(Volta
g
e
adjust)
0 to 200% % 1 100
F31 (Function)
0: Output frequenc
y
1: Output current
2: PID feedback amount
3: DC link circuit volta
g
e
-- 0
F36
30R
y
operation
mode
0: Excited when tripped
1: Normall
y
excited
-- 0 X
E: Extension Terminal Functions
Func-
tion
code
No.
Name Settin
g
ran
g
e Unit
Min.
unit
Factor
y
settin
g
Chan
g
e
durin
g
opera-
tion
User
set-
tin
g
E01 X1 terminal
(function
selection)
X2 terminal
(function
selection)
X3 terminal
(function
selection)
Use the code values listed below to select
[X1], [X2] and [X3] terminal functions.
-- 0 X
E02 - - 2 X
E03 - - 3 X
0: Multistep frequenc
y
1 (SS1)
1: Multistep frequenc
y
2 (SS2)
2: Coast-to-stop command (BX)
3: Alarm reset (RST)
4: External alarm (THR)
5: Write enable command for ke
y
pad
(WE-KP)
6: PID control cancel (Hz/PID)
7: Link operation selection (LE)