4 Safet
y
Instructions
FVR-C11S-EN
Compliance with low volta
g
e directive in EU [Continued]
Use of wires specified in Appendix C of EN 60204 is recommended.
Power
suppl
y
volta
g
e
Nominal
applied
motor
[kW]
Inverter t
y
pe
Molded case circuit
breaker (MCCB) or
earth leaka
g
e
circuit breaker
(ELCB)
1
)
Rated current [A]
Recommended wire size [mm
2
]
Input circuit
2
)
sin
g
le phase
200V [L1/L, L2/N]
Output
circuit
2
)
[U, V, W]
DCR
2
)
circuit
[P1]
[P(+)]
Control
wirin
g
With
DCR
Without
reactor
3
)
With
DCR
Without
reactor
3
)
Sin
g
le
phase
200V
0.1 FVR0. 1C11S-7EN
6
6
2.5
4
)
2.5
4
)
2.5
4
)
2.5
4
)
0.5
0.2 FVR0. 2C11S-7EN
0.4 FVR0. 4C11S-7EN 10
0.75 FVR0. 75C11S-7EN 10 16
1.5 FVR1. 5C11S-7EN 16 20
4.0
4
)
2.2 FVR2. 2C11S-7EN 20 32
4.0
5
)
6.0
5
)
2.5
5
)
4.0
5
)
1) The applicable frame and series of the molded case circuit breaker (MCCB) and
earth leaka
g
e circuit breaker (ELCB) var
y
accordin
g
to the capacit
y
of the
transformer of the equipment. For details of selection, refer to the concernin
g
technical documents.
2) The recommended wire size for the main circuit is the case for the low volta
g
e
directive at ambient temperature 40 °C.
3) The power suppl
y
impedance without a reactor is considered to be the
equivalent of 0.1% of the inverter capacit
y
, with 10% current imbalance
accompanied b
y
the volta
g
e imbalance.
4) Crimp terminals up to 7.4 mm in width (includin
g
tolerance) can be used.
5) Crimp terminals up to 9.5 mm in width (includin
g
tolerance) can be used.
6) Use the
g
roundin
g
cable of a size equal to or lar
g
er than that of the input power
suppl
y
cable.
CAUTION