4 Safet
Instructions
FVR-C11S-EN
Compliance with low volta
e directive in EU [Continued]
Use of wires specified in Appendix C of EN 60204 is recommended.
Power
suppl
volta
e
Nominal
applied
motor
[kW]
Inverter t
pe
Molded case circuit
breaker (MCCB) or
earth leaka
e
circuit breaker
(ELCB)
1
Rated current [A]
Recommended wire size [mm
2
]
Input circuit
2
sin
le phase
200V [L1/L, L2/N]
Output
circuit
2
[U, V, W]
DCR
2
circuit
[P1]
[P(+)]
Control
wirin
With
DCR
Without
reactor
3
With
DCR
Without
reactor
3
Sin
le
phase
200V
0.1 FVR0. 1C11S-7EN
6
6
2.5
4
2.5
4
2.5
4
2.5
4
0.5
0.2 FVR0. 2C11S-7EN
0.4 FVR0. 4C11S-7EN 10
0.75 FVR0. 75C11S-7EN 10 16
1.5 FVR1. 5C11S-7EN 16 20
4.0
4
2.2 FVR2. 2C11S-7EN 20 32
4.0
5
6.0
5
2.5
5
4.0
5
1) The applicable frame and series of the molded case circuit breaker (MCCB) and
earth leaka
e circuit breaker (ELCB) var
accordin
to the capacit
of the
transformer of the equipment. For details of selection, refer to the concernin
technical documents.
2) The recommended wire size for the main circuit is the case for the low volta
e
directive at ambient temperature 40 °C.
3) The power suppl
impedance without a reactor is considered to be the
equivalent of 0.1% of the inverter capacit
, with 10% current imbalance
accompanied b
the volta
e imbalance.
4) Crimp terminals up to 7.4 mm in width (includin
tolerance) can be used.
5) Crimp terminals up to 9.5 mm in width (includin
tolerance) can be used.
6) Use the
roundin
cable of a size equal to or lar
er than that of the input power
suppl
cable.