Safet
Instructions 3
FVR-C11S-EN
Compliance with low volta
e directive in
EU [Applicable to products with T
V
mark]
CAUTION
1. Safe separation for control interface of this
inverter is provided when this inverter is in-
stalled in overvolta
e cate
or
II. PELV
(Protective Extra Low Volta
e) circuit or
SELV (Safet
Extra Low Volta
e) circuit
from external controller is connected to the
interface directl
.
2. Basic insulation for control interface of this
inverter is provided when this inverter is in-
stalled in overvolta
e cate
or
III. An insu-
lation transformer has to be installed
between power suppl
mains and this in-
verter when SELV circuit from external
controller is connected to this inverter di-
rectl
. Otherwise supplementar
insulation
between control interface of this inverter
and environment must be provided.
3. The
round terminal G should alwa
s be
connected to the
round. Don’t use onl
RCD as the sole method of electric shock
protection. Dimensions of external PE con-
ductor should be same as dimensions of
input phase conductor and capable for
possible fault.
4. Use MCCB or MC that conforms to EN or
IEC standard.
5. Where RCD (Residual-current-operated
protective device) is used for protection in
case of direct or indirect contact, onl
RCD
of t
pe B is allowed on the suppl
side of
this EE (Electric equipment). Otherwise an-
other protective measure shall be applied
such as separation of the EE from the en-
vironment b
double or reinforced insula-
tion or isolation of EE and suppl
s
stem
b
the transformer.
6. The inverter has to be installed in environ-
ment of pollution de
ree 2. If the environ-
ment is pollution de
ree 3 or 4, the
inverter has to be installed in a cabinet of
IP54 or hi
her.
7. Use a prescribed wire accordin
to the
EN60204 Appendix C.
8. Install the inverter, AC or DC reactor, out-
put filter in an enclosure that meets the
followin
requirement, to prevent a hu-
man bod
from touchin
directl
to these
equipment.
1) When a person can touch easil
on each
connectin
terminal or live parts, install
the inverter, AC or DC reactor, output fil-
ter in an enclosure with minimum de-
ree of protection of IP4X.
2) When a person can not touch easil
on
each connectin
terminal or live parts,
install the inverter, AC or DC reactor,
output filter in an enclosure with a mini-
mum de
ree of protection of IP2X.
9. It is necessar
to install the inverter in ap-
propriate method usin
an appropriate
RFI filter to conform to the EMC directive.
It is customer’s responsibilit
to check
whether the equipment, the inverter is in-
stalled in, conforms to EMC directive.