Fulton ProtoNode Start-up Guide
Page 10 of 47
3.3 Configuring Modbus Device Communications
3.3.1 Confirm the Device and ProtoNode COM Settings Match
Any connected serial devices MUST have the same baud rate, data bits, stop bits, and
parity settings as the ProtoNode.
Figure 4 specifies the device serial port settings required to communicate with the ProtoNode.
Port Setting
Device
Protocol
Modbus RTU
Baud Rate
19200
Parity
None
Data Bits
8
Stop Bits
1
Figure 4: COM Settings
3.3.2 Set Node-ID for Any Device Attached to the ProtoNode
Set Node-ID for any device attached to ProtoNode. The Node-ID needs to be uniquely assigned between
1 and 255.