VMP-IOMM-2018-2
Fulton Ltd
Page 96
APPENDIX - D
1.2 WEEKLY TEST IN ADDITION
1.2.1 LOW WATER WEEKLY IN ADDITION
1. Switch the Pump switch to the Pump OFF position.
2. By evaporation, lower the water level in the boiler until the Low Water alarm sounds, the Low
Water Reset buttons illuminate, and the burner shuts down.
3. Switch the Pump switch to the ON position.
4. The pump will start and restore the water level to the normal position and switch off.
5. After approximately 17 seconds from restoring the Low Water level the Low Water Relay can
be reset.
6. To cancel the Low Water Level alarm and light, press the Low Water Reset button.
The burner will restart.