TROUBLESHOOTING - 6
249/254
Building Technologies Division Basic documentation LMV26... CC1P7547en
30 Error code list 20.04.2016
Error code Diagnostic code Meaning for the LMV26... system Remedy
first curve settings
Bit 0
Valency 1
No operating mode selected
Bit 1
Valency 2..3
No fuel train defined
Bit 2
Valency 4..7
No curves defined
Bit 3
Valency 8..15
Standardized speed undefined
Bit 4
Valency 16..31
Backup / restore was not possible
202 # Internal error operating mode selection Redefine the operating mode (parameter 201)
203 # Internal error
Redefine the operating mode (parameter 201).
Make a reset; if error occurs repeatedly, replace the unit
204 Phase number Program stop Program stop is active (no error)
205 # Internal error Make a reset; if error occurs repeatedly, replace the unit
206
0
Inadmissible combination of units
(basic unit – AZL2...)
207 # Version compatibility basic unit – AZL2...
0 Basic unit version too old
1 AZL2... version too old
208 # Internal error Make a reset; if error occurs repeatedly, replace the unit
209 # Internal error Make a reset; if error occurs repeatedly, replace the unit
210
0 Selected operating mode is not released for the basic unit
Select a released operating mode for the basic unit
240 # Internal error Make a reset; if error occurs repeatedly, replace the unit
245 # Internal error Make a reset; if error occurs repeatedly, replace the unit
250 # Internal error Make a reset; if error occurs repeatedly, replace the unit