FusionServer 2288H V5 Server
Technical White Paper
Copyright © xFusion Digital Technologies Co., Ltd.
NOTE
The highest operating temperature varies depending on the
server configuration. For details, see A.3 Operating Temperature
Limitations .
Relative humidity (RH,
non-condensing)
⚫
Operating humidity: 8% to 90%
⚫
Storage humidity (within three months): 8% to 85%
⚫
Storage humidity (within six months): 8% to 80%
⚫
Storage humidity (within one year): 20% to 75%
⚫
Maximum change rate: 20%/h
≥ 204 cubic feet per minute (CFM)
≤3050m
⚫
When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature
decreases by 1°C (1.8°F) for every increase of 300 m
(984.25 ft).
⚫
When the configuration complies with ASHRAE Class
A3 standards and the altitude is above 900 m (2952.76
ft.), the highest operating temperature decreases by
1°C (1.8°F) for every increase of 175 m (574.14 ft.).
⚫
When the server configuration complies with ASHRAE
Class A4 and the altitude is above 900 m (2952.76 ft),
the highest operating temperature decreases by 1°C
(1.8°F) for every increase of 125 m (410.1 ft).
⚫
HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
⚫
Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
⚫
Silver corrosion rate test: 200 Å/month
⚫
The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
⚫
There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the equipment
room be monitored by a professional agency.
The declared A-weighted sound power levels (LWAd) and
declared average bystander position A-weighted sound
pressure levels (LpAm) listed are measured at 23°C
(73.4°F) in accordance with ISO 7779 (ECMA 74) and
reported in accordance with ISO 9296 (ECMA 109).
⚫
Idle: