12
• System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH
• ESL models 429AT, 521B, 521BXT—(models 521B and 521BXT require the following dip
switch settings: 1-on, 2-off)
Use only the 2-wire smoke detector models described above. Alarm signals from other
detectors may not be processed correctly if the panel has lost AC power and is operat-
ing only from the backup battery.
When set up for 2-wire smoke detectors, zone 8 can handle up to 10 smoke detectors with
120 uA maximum idle current per detector. Maximum total loop current allowed in an alarm con-
dition is 100 mA. Connect one or more, 2-wire smoke detectors to the panel as shown in Figure
11.
Note
The Two-Wire Smoke set-
ting (in program mode) must
be off when using 4-wire
smoke detectors. See
ONBOARD OPTIONS—INPUTS
in the section “Programming
the Panel” for complete
details.
Connecting 4-Wire Smoke Detectors
Zone input 8 can be used with 4-wire smoke detectors that latch and remain in the alarm state
until power is removed, then restored to the detector. The panel provides this power interruption
from terminal 23 (2-wire smoke power +), provided that zone 8 is learned into sensor group 26
(fire).
Note
Zone 8 must be learned into
sensor group 26 (fire) for
connected smoke detectors
to reset after canceling a fire
alarm.
Table 5 describes the minimum available panel power. Use only 4-wire smoke detectors that
operate at these power limits. Connect up to five Sentrol (ESL) model 449AT (part no. 13-360)
smoke detectors to panel power and zone 8 input as shown in Figure 12.
Connecting Speakers
The panel provides one siren driver output for intrusion (steady), fire (temporal 3), and auxiliary
(on-off-on-off) alarm sounds. This output trips only for partition 1 alarms.
2 2
2 3
Z O N E
8
+ 1 2 V
2 W S M K
+
-
+
-
Panel
Terminals
2k Ohm EOL
(Locate at Last Detector)
Resistor 49-454
Figure 11. Connecting 2-Wire Smoke Detectors
to the Panel
2k Ohm EOL
(Locate at Last Detector)
Resistor 49-454
Model
449AT
Model
449AT
GND
Zone
7
Zone
8
+12V
2W SMK
Figure 12. Connecting 4-Wire Smoke
Detectors to Panel Power and Zone 8 Input
Table 5: Panel Minimum Available Power
Min. Voltage/Max. Current Available
8.3 VDC, up to 30 mA total (combined alarm) current
8.1 VDC, up to 40 mA total (combined alarm) current
7.7 VDC, up to 60 mA total (combined alarm) current
7.4 VDC, up to 80 mA total (combined alarm) current
Caution
!