63
Testing Outputs and Sirens
All outputs (onboard and SnapCard) should be tested to verify configuration programming.
Be sure to contact the central monitoring station before activating outputs that trigger
from an alarm condition.
¾To test outputs:
1. Contact the central monitoring station to inform them you are testing the system.
2. Verify that all wiring at the panel and output devices is correct.
3. Activate the appropriate device to trigger each output as programmed.
4. Verify that each output responds according to the programmed configuration number. For
outputs that trigger sirens, verify that the correct alarm sounds are produced from these
sirens. Table 12 describes the system alarm sounds you should hear for each alarm event.
5. Contact the central monitoring station when you are finished testing.
Testing Light Control
Test all lights plugged into X-10 Lamp Modules to verify house code and light number settings.
¾
To test light control:
1. Press 0 + 0 repeatedly to turn all lights on and off together.
2. Press 0 + 1 repeatedly to turn light 1 on and off.
3. Repeat step 2 for remaining lights (0 + 2 for light 2, 0 + 3 for light 3, etc.).
4. Arm the system to Away. All lights plugged into modules set to Unit 1 (or set as entry lights)
should turn on and stay on for 5 minutes. All lights plugged into modules set to Unit 2
should blink three times to indicate the arming level. Remaining lights should not be
affected.
5. Disarm the system. If Unit 1 (or entry) lights were on for an entry or alarm, they will turn off
in 5 minutes. Unit 2 lights should blink once to indicate the system is off. Remaining lights
should not be affected.
6. All lights should turn on and remain on during fire and auxiliary/medical alarms. All lights
should flash during a police or intrusion alarm.
Testing the Energy Saver Module (ESM)
Test the Energy Saver Module to verify it overrides the thermostat.
Note
The system must have high-
and low-temperature limits
set to test the Energy Saver
Module.
¾To test the Energy Saver Module:
1. Press * (status) + * (status) to display the system status, ENERGY SAVER OFF, and the present
TEMPERATURE nn°. The temperature displayed (and/or announced) should match the house
thermostat. If the temperatures do not match, refer to the
ACCESSORY MODULES—BUS
DEVICES
menu in the “Programming” section.
679 Installer Code used
680 Dealer Code used
697 Quick Arm used
698 Keyswitch Sensor used
699 System Armed Itself (during service or power-up)
Table 12: System Alarm Sounds
Alarm Type Alarm Sound
Fire Repeating series of three beeps
Police/Intrusion Continuous tone
Auxiliary Rapid beeps
Table 11: Pager Sensor/Zone Code and Numbers
Code Sensor/Zone or User Number
Caution
!