52
6. Press # to accept the displayed choice and the display shows: OUTPUT N ITEM 1 0 -.
7. Repeat steps 4 and 5 as needed to complete the output name.
8. Press
* after entering the last character or word number. The display shows the complete text
name. For example:
OUTPUT 1 GARAGE DOOR.
Onboard Options Menu
The ONBOARD OPTIONS menu lets you set up the following built-in options:
INPUTS—This menu lets you turn the Smoke Verification and the Two Wire Smoke features
off or on.
OUTPUT PROGRAMMING—This menu lets you set configuration numbers for the two built-in
panel outputs and assign the outputs to partitions.
OUTPUT TEXT—This menu lets you assign text to the output allowing the output to be con-
trolled by the user.
The following sections describe the settings that appear under
ONBOARD OPTIONS—INPUTS.
Smoke Verify (Onboard Options—Inputs)
(1100)
(Default = off) This setting determines whether the panel requires one alarm signal (off) or two
alarm signals (on) within five minutes before activating system sirens and reporting to a central
station. This setting affects 2-wire and 4-wire smoke detectors connected to SnapCard or onboard
zone inputs that are learned into sensor group 26 (FIRE).
Note
For California State Fire
Marshall (CSFM) Listed
installations, Smoke Verify
must be set to off.
¾To turn Smoke Verify off or on:
1. With the display showing ONBOARD OPTIONS, press # twice. The display shows SMOKE VER-
IFY OFF/ON
(current setting).
2. Press 1 (off) or 2 (on). The display flashes the entered number. Press # and the display shows
the new setting.
Two Wire Smoke (Onboard Options—Inputs)
(1101)
(Default = off) This setting determines how onboard hardwire zone 8 is configured. When this
setting is on, zone 8 will be configured for two wire smoke detectors. When off, it will be config-
ured for a normal hardwire input.
¾
To turn Two Wire Smoke off or on:
1. With the display showing ONBOARD OPTIONS, press # twice. The display shows SMOKE VER-
IFY OFF/ON (current setting).
2. Press A or B until the display shows
TWO WIRE SMOKE ON/OFF (current setting).
3. Press 1 (off) or 2 (on). The display flashes the entered number. Press # and the display shows
the new setting.
The following sections describe the settings that appear under
ONBOARD OPTIONS—OUTPUT PRO-
GRAMMING
.
Output 1, 2 (Onboard Options—Output—Programming)
Output 1: partition assign—11100, configuration—11101
Output 2: partition assign11110, configuration11111
(Defaults: Output 1 = Ptn 1, 01614; Output 2 = Ptn. 1, 01710) This setting lets you assign the par-
tition and the 5-digit configuration number. The configuration number determines
which system event activates the selected output, and
the duration or time the output is activated.
The first three digits represent the trigger number of an event (such as triggering an alarm, open-
ing a sensor, or arming the system). The last two digits represent how the output responds (such
as momentary switching, maintained (or latched) switching, or switching for a preset time).
Note
If you want to configure an
output for user Output Con-
trol you must use the Output
Text feature to name the out-
put. If no Output Text is pro-
grammed, Output Control
will not function for that out-
put.
Use the system event trigger and response numbers listed in Appendix B: Reference Tables.
¾
To set up onboard Output 1 & 2 partition and configuration assignments:
1. With the display showing ONBOARD OPTIONS, press # + B. The display shows OUTPUT PRO-
GRAMMING
.
2. Press # and the display shows
OUTPUT 1. Press B to select OUTPUT 2.
3. Press # and the display shows PARTITION ASSIGN n (current setting).
4. Press 1 or 2 to assign the output to the desired partition, then press #. The display shows PAR-
TITION ASSIGN (new setting).