37
Output Trip Time (Timers—Global)
(0304)
(Default = 4 sec) This setting determines how long outputs are activated when tripped (if they are
configured for a momentary response).
¾
To set the Output Trip Time:
With the display showing OUTPUT TRIP TIME nn SECS (current setting), enter the number of
seconds (1–12). The display flashes the entered setting. Press # and the display shows the
new setting.
Activity Timeout (Timers—Global)
(0305)
(Default = 24 hours) This setting determines when the system sends a “no activity” report. The
panel can be set to wait from 1–42 hours. If no user interaction or device activation occurs in that
time, the panel sends a report to the central station.
¾
To set the Activity Timeout:
With the display showing ACTIVITY TIMEOUT nn HOURS (current setting), enter the number of
hours (1–42). The display flashes the entered setting. Press # and the display shows the new
setting.
Daylight Saving (Timers—Global)
(0306)
(Default = on) When this setting is on, the panel clock automatically adjusts for daylight saving
time changes.
¾
To turn Daylight Saving off or on:
With the display showing DAYLIGHT SAVING OFF/ON (current setting), press 1 (off) or 2 (on).
The display flashes the entered setting. Press # and the display shows the new setting.
The following sections describe the timer settings that appear under
PARTITION 1-2.
Entry Delay (Timers—Partition 1-2)
(partition 1: 0310, partition 2: 0320)
(Default = 32 sec) This setting determines how much time the user has to disarm the system
(after entering the armed premises through a “designated delay door”) without causing an alarm.
Note
For residential UL Listed
installations, the Entry Delay
must be set to 45 seconds or
less.
¾To set the Entry Delay:
With the display showing ENTRY DELAY nnn SECS (current setting), enter the desired time
value (32–240 using 8-second intervals). The display flashes the entered setting. Press # and
the display shows the new setting.
Exit Delay (Timers—Partition 1-2)
(partition 1: 0311, partition 2: 0321)
(Default = 64 sec) This setting determines how much time the user has (after arming the system)
to leave the premises through a “designated delay door” without causing an alarm.
Note
For residential UL Listed
installations, the Exit Delay
must be set to 60 seconds or
less.
¾To set the Exit Delay:
With the display showing EXIT DELAY nnn SECS (current setting), enter the desired time value
(48–184 using 8-second intervals). The display flashes the entered setting. Press # and the
display shows the new setting.
Extended Delay (Timers—Partition 1-2)
(partition 1: 0312, partition 2: 0322)
(Default = 4 minutes) This setting determines how much time the user has (after arming the sys-
tem) to enter or exit the premises through a “designated extended delay door” (1–8 minutes).
Note
For UL Listed installations
Extended Delay may not be
used.
¾To set the Extended Delay:
With the display showing EXTENDED DELAY n MINUTES (current setting), enter the desired
time value (1–8). The display flashes the entered setting. Press # and the display shows the
new setting.
Siren Timeout (Timers—Partition 1-2)
(partition 1: 0313, partition 2: 0323)
(Default = 4 minutes) This setting determines how long sirens sound (1–30 minutes) if no one is
present to disarm the system.