Reporting Menu
The REPORTING menu lets you set up which system events are reported to the central monitoring
station. The following describes how to program the reporting settings that appear under
GLOBAL.
Star Is No Delay (partiton 1: 0514, partition 2: 0524)
Touchpad Options-Partitions 1-2 (Default = off)
This setting determines whether the keychain touchpad star button
controls an output (off) or the No Delay feature (on).
¾
To change the keychain Star Is No Delay setting:
1. With the display showing STAR IS NO DELAY OFF/ON
(current setting), press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new setting.
24-Hour Tamper (06000)
Reporting-Global (Default = off)
When this setting is on, the panel sounds sirens and reports a tamper
alarm (even when the system is disarmed), when wireless sensor
tamper switches are activated.
Note
For commercial UL Listed installations (UL 1610) the 24-Hour Tamper
must be set to on.
¾To turn 24-Hour Tamper off or on:
1. With the display showing 24 HOUR TAMPER OFF/ON
(current setting), press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new setting.
Buffer Control (06001)
Reporting-Global (Default = off)
When this setting is on, only arming level changes are logged in the
buffer (memory) of the panel. When this setting is off, all system
events are logged in the buffer.
¾
To turn Buffer Control off or on:
1. With the display showing BUFFER CONTROL OFF/ON
(current setting), press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new setting.
Back In Service (06002)
Reporting-Global (Default = on)
When this setting is on, the panel reports to the central station when
AC and backup battery power are restored (after an extended power
outage).
¾
To turn Back In Service reports off or on:
1. With the display showing BACK IN SERVICE OFF/ON
(current setting), press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new setting.
Bypass Reports (06003)
Reporting-Global (Default = off)
When this setting is on, the panel reports to the central station
whenever sensors or zones are bypassed.
¾
To turn Bypass Reports off or on:
1. With the display showing BYPASS REPORTS OFF/ON
(current setting), press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new setting.
Low CPU Battery (06004)
Reporting-Global (Default = on)
When this setting is on, the panel reports a low panel battery to the
central station before shutting down.
Note
For UL 1635 listed installations, the Low CPU Battery feature must be
set to on.
¾To turn Low CPU Battery reports off or on:
1. With the display showing LOW CPU BATTERY OFF/
ON (current setting), press 1 (off) or 2 (on). The dis-
play flashes the entered setting.
2. Press # and the display shows the new setting.